Electric Modicon X80 Digital Input Module | Schneider BMXSDI1602
Electric Modicon X80 Digital Input Module | Schneider BMXSDI1602
Electric Modicon X80 Digital Input Module | Schneider BMXSDI1602
/ 3

Electric Modicon X80 Digital Input Module | Schneider BMXSDI1602

  • Manufacturer: Schneider

  • Part Number: BMXSDI1602

  • Condition:New with Original Package

  • Product Type: Electric Modicon X80 Digital Input Module

  • Country of Origin: USA

  • Payment:T/T, Western Union

  • Shipping port: Xiamen

  • Warranty: 12 months

Product Description

The Schneider Electric BMXSDI1602 is a discrete input module from the Modicon X80 platform. It is designed for reliable signal acquisition within Modicon M340 and M580 PLC systems.

This module provides sixteen non-isolated digital inputs operating at 24 V DC positive logic. Therefore, it supports direct connection of standard industrial sensors and switching devices.

The BMXSDI1602 accepts signals from two-wire and three-wire proximity sensors compliant with IEC 60947-5-2. Moreover, integrated diagnostics improve transparency during commissioning and routine operation.

Thanks to fast response times and stable current thresholds, this module ensures accurate detection of field signals. In addition, its compact X80 format simplifies system expansion without increasing cabinet complexity.

Technical Specifications

General Information

  • Manufacturer: Schneider Electric

  • Product range: Modicon X80

  • Product type: Discrete input module

  • Model: BMXSDI1602

  • Compatible PLCs: Modicon M340, Modicon M580

Input Characteristics

  • Number of inputs: 16

  • Input type: Discrete, non-isolated

  • Logic type: Current sink (logic positive)

  • Rated input voltage: 24 V DC positive

  • Input voltage range: 19…30 V DC

  • Input current: 3.2 mA

  • Input impedance: 7,500 Ω

Signal Thresholds

  • Current state 1 guaranteed: ≥ 2 mA

  • Current state 0 guaranteed: ≤ 1.5 mA

  • Voltage detection threshold:

  • < 14 V DC indicates sensor fault

Performance Data

  • Typical response time: 6 ms

  • Maximum response time: 6 ms

  • Paralleling of inputs: Supported

Power and Reliability

  • Typical current consumption:

    • 256 mA at 3.3 V DC

    • 100 mA at 24 V DC

  • Power dissipation: 3.57 W

  • MTBF: 265,000 hours

Protection and Diagnostics

  • Protection type: Reverse polarity protection

  • External overload protection: 0.5 A fast-blow fuse

  • Status indicators:

    • 1 green RUN LED for module operation

    • 1 green LED per input channel

    • 1 red ERR LED for module error

    • 1 red I/O LED for input fault

Environmental and Mechanical

  • Operating temperature: –25…60 °C

  • Storage temperature: –40…85 °C

  • Relative humidity: 5–95% non-condensing

  • Mounting: X80 backplane, DIN rail or panel

  • Net weight: 0.115 kg (0.254 lb)

Compliance

  • Insulation resistance: > 10 MΩ at 500 V DC

  • Certifications: CE, UL, CSA, EAC

  • Lifecycle status: Active product in Modicon X80 portfolio

FAQ

Q1: Is the BMXSDI1602 input module isolated?
A1: No, the inputs are non-isolated and designed for common reference applications.

Q2: What sensor types are compatible with this module?
A2: It supports two-wire and three-wire proximity sensors compliant with IEC 60947-5-2.

Q3: What PLC platforms support the BMXSDI1602?
A3: The module is compatible with Modicon M340 and Modicon M580 PLC systems.

Q4: Does the module include diagnostic indicators?
A4: Yes, it includes per-channel LEDs and module-level RUN and ERR indicators.

Q5: Is the BMXSDI1602 still actively supported by Schneider Electric?
A5: Yes, it remains an active product within the Modicon X80 portfolio.