TM3AM6 by Schneider Electric | 4AI 2AO Analog Expansion Module
Manufacturer: Schneider
-
Part Number: TM3AM6
Condition:New with Original Package
Product Type: 4AI 2AO Analog Expansion Module
-
Country of Origin: France
Payment:T/T, Western Union
Shipping port: Xiamen
Warranty: 12 months
Schneider Electric TM3AM6 Mixed Analog I/O Module – Product Description
Overview
The Schneider Electric TM3AM6 module extends Modicon M221, M241, M251, and M262 systems with reliable mixed analog I/O. It offers four analog inputs and two analog outputs that support both current and voltage signals, allowing engineers to handle measurement and actuation within one compact module. Moreover, its stable 12-bit resolution helps maintain accurate control in fast-moving automation environments. The TM3 expansion bus ensures simple installation, therefore reducing engineering time and panel complexity.
Technical Specifications
Electrical & I/O
-
Total analog channels: 6 (4 inputs + 2 outputs)
-
Supply voltage: 24 VDC via TM3 bus
-
Input ranges: 0–10 V, 0–20 mA, 4–20 mA
-
Output ranges: 0–10 V, 0–20 mA, 4–20 mA
-
Resolution: 12 bits (inputs and outputs)
-
Accuracy: ±0.5% full scale (typical)
-
Input impedance: ≥100 kΩ (voltage), approx. 250 Ω (current)
-
Output load: ≥1 kΩ (voltage), ≤500 Ω (current)
-
Isolation: 500 V between analog circuits and logic
Performance
-
Conversion time: around 1 ms per channel
-
Sampling rate: up to 1 kHz depending on PLC
-
Diagnostics: module and channel LEDs
Mechanical
-
Dimensions: 23.6 × 90 × 70 mm
-
Weight: 0.11 kg
-
Mounting: DIN-rail (TH35-15 / TH35-7.5)
-
Protection rating: IP20
-
Terminal type: removable screw connectors
Environmental & Compliance
-
Operating temperature: 0 °C to +55 °C
-
Storage temperature: –20 °C to +70 °C
-
Humidity: 5–95% non-condensing
-
Standards: IEC 61131-2
-
Certifications: CE, UKCA, RCM, EAC, cULus, cULus HazLoc
-
ESD immunity: 8 kV air, 4 kV contact
-
Magnetic field immunity: 30 A/m (IEC 61000-4-8)
FAQ
Q1: Which PLCs are supported?
It works with Modicon M221, M241, M251, and M262 controllers via the TM3 bus.
Q2: Can I mix voltage and current modes on different channels?
Yes. Each channel may be configured independently inside the software.
Q3: Are the outputs protected against overloads?
The module supports standard industrial loads as long as they remain within the listed ranges.
Q4: What software is used to configure the TM3AM6?
Configuration is performed through EcoStruxure Machine Expert or Machine Expert – Basic.
Q5: Does the module require external power for analog outputs?
No. The TM3 bus supplies power for the module logic, while load devices still use their own supply