GE Fanuc IC693ALG390F Analog Module | New & Original Stock
GE Fanuc IC693ALG390F Analog Module | New & Original Stock
GE Fanuc IC693ALG390F Analog Module | New & Original Stock
/ 3

GE Fanuc IC693ALG390F Analog Module | New & Original Stock

  • Manufacturer: GE Fanuc

  • Part Number: IC693ALG390F

  • Condition:New with Original Package

  • Product Type: Analog Output Modules

  • Country of Origin: USA

  • Payment:T/T, Western Union

  • Shipping port: Xiamen

  • Warranty: 12 months

GE Fanuc IC693ALG390F Analog Output Module

The GE Fanuc IC693ALG390F, also cataloged as the IC693ALG390 2-Channel Analog Voltage Output Module, operates as a dedicated hardware component for converting digital values into analog signals within GE Fanuc Series 90-30 PLC platforms.

Hardware Specifications

Parameter Specification
Model IC693ALG390F / IC693ALG390
Brand GE Fanuc (Emerson Automation)
Origin USA
Weight 0.4 kg (0.88 lbs)
Dimensions 152.4 mm x 152.4 mm x 50.8 mm (6.0 in x 6.0 in x 2.0 in)
Operating Temp 0 to 60 deg C
Power Consumption Determined by active 18 to 30 VDC external field supply
Signal Range -10 to +10 VDC
Number of Channels 2 analog voltage output channels
Resolution 2.5 mV per count
Calibration Factory calibrated to 2.5 mV per count
Accuracy +/- 5 mV at 25 deg C
Temperature Offset 1 mV maximum from 0 to 60 deg C
Update Rate 5 ms for all channels
Galvanic Isolation 1500 V RMS field side to logic side
External Supply 18 to 30 VDC, 10% maximum ripple

Backplane Bus Communication Velocity and I/O Density Scaling

The GE Fanuc IC693ALG390F interfaces with the parallel Series 90-30 backplane bus to transfer 12-bit digital profiles into internal digital-to-analog converter registers. The module maintains a deterministic 5 ms update rate across both voltage channels simultaneously, ensuring output tracking stability regardless of changes in backplane bus communication velocity or active network nodes. Galvanic isolation circuits rated at 1500 V RMS physically decouple the field terminal connections from the internal logic bus to suppress common-mode noise and safeguard the main PLC processor from field-side voltage spikes during complex system I/O density scaling.

Frequently Asked Questions

Q: Does this module draw its operational loop power directly from the 90-30 backplane? A: No. The internal digital-to-analog conversion circuits and analog output loops are powered via an external 18 to 30 VDC field supply connected to the terminal block. The module only draws a minimal logic-level initialization current from the backplane +5 VDC line.

Q: What happens to the voltage outputs if the PLC enters a Stop mode or backplane communications fail? A: Upon a loss of backplane data transmission or CPU stop command, the digital-to-analog converters lose active register updates. The analog circuits drop the physical output values to a default safe state (0 VDC) to prevent downstream actuators or positioning loops from maintaining obsolete setpoints.

Field Installation Guidelines

  • Field Power Isolation Requirements: De-energize both the backplane chassis power and the 24 VDC external field power loop before attaching or removing the field wiring connector terminal block to prevent active channel arcing.
  • Shield Terminal Termination: Connect the braided shield of the shielded twisted-pair signal cables directly to the chassis ground bar or designated shield terminals on the rack. Do not allow shield braids to remain floating or touch live electrical components.
  • External Voltage Specifications: Ensure the external DC supply provides a regulated voltage between 18 and 30 VDC. The supply must not exhibit a voltage ripple exceeding 10% to prevent degradation of the factory accuracy threshold (+/- 5 mV).