{"product_id":"allen-bradley-1769sc-if8u-8-channel-universal-analog-module","title":"Modul Analog Universal 8-Kanal Allen-Bradley 1769sc-IF8U","description":"\u003ch2\u003eAllen-Bradley 1769sc-IF8U CompactLogix Universal Analog Input Module\u003c\/h2\u003e\n\u003cp\u003eThe \u003cstrong\u003eAllen-Bradley 1769sc-IF8U\u003c\/strong\u003e serves as the primary \u003cstrong\u003e1769sc-IF8\u003c\/strong\u003e Universal Analog Input Module utilized to execute multi-channel signal conversion and isolation across CompactLogix and MicroLogix 1500 platforms. The internal hardware framework incorporates a 16-bit analog-to-digital converter capable of acquiring inputs from up to eight voltage, current, or thermocouple channels, or up to four RTD and resistance sensors. Operating as a single-slot chassis component, the module provides programmable digital filtering alongside dedicated cold junction compensation to manage thermal sensor linearized offsets directly at the backplane interface boundary.\u003c\/p\u003e\n\u003ch3\u003eHardware Specifications\u003c\/h3\u003e\n\u003cfigure class=\"table\"\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr\u003e\n\u003cth\u003e\u003cstrong\u003eParameter\u003c\/strong\u003e\u003c\/th\u003e\n\u003cth\u003e\u003cstrong\u003eSpecification\u003c\/strong\u003e\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003eModel\u003c\/td\u003e\n\u003ctd\u003e1769sc-IF8U\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eBrand\u003c\/td\u003e\n\u003ctd\u003eAllen-Bradley\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOrigin\u003c\/td\u003e\n\u003ctd\u003eUSA\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eWeight\u003c\/td\u003e\n\u003ctd\u003e0.26 kg (0.56 lbs)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eDimensions\u003c\/td\u003e\n\u003ctd\u003eSingle-slot standard 1769 width form factor\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOperating Temp\u003c\/td\u003e\n\u003ctd\u003e0 to +60 deg C\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003ePower Consumption\u003c\/td\u003e\n\u003ctd\u003eBackplane current: 150 mA at 5 VDC, 45 mA at 24 VDC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eThermal Dissipation\u003c\/td\u003e\n\u003ctd\u003eApproximately 3 W\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eChannel Count\u003c\/td\u003e\n\u003ctd\u003e8 analog inputs (V, I, TC) or 4 RTD\/Resistance inputs\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eInput Resolution\u003c\/td\u003e\n\u003ctd\u003e16-bit\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eVoltage Input Ranges\u003c\/td\u003e\n\u003ctd\u003e±50 mV, ±100 mV, 0-5 V, 1-5 V, 0-10 V, ±10 V\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eCurrent Input Ranges\u003c\/td\u003e\n\u003ctd\u003e0-20 mA, 4-20 mA\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eResistance Ranges\u003c\/td\u003e\n\u003ctd\u003e0-150, 0-1000, 0-3000 ohms\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eThermocouple Types\u003c\/td\u003e\n\u003ctd\u003eJ, K, T, B, E, R, S, N, C\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eRTD Sensor Types\u003c\/td\u003e\n\u003ctd\u003ePT385\/3916, Ni618\/672, NiFe518, Cu426\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eUpdate\/Sample Times\u003c\/td\u003e\n\u003ctd\u003e0.30 s at 10 Hz, 0.63 s at 50 Hz, 0.53 s at 60 Hz, 0.15 s at 250 Hz, 0.07 s at 1000 Hz\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eInput Overvoltage Max\u003c\/td\u003e\n\u003ctd\u003e±30 VDC continuous\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eInput Overcurrent Max\u003c\/td\u003e\n\u003ctd\u003e28 mA continuous\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eElectrical Isolation\u003c\/td\u003e\n\u003ctd\u003e10 VDC channel-to-channel, 500 VDC field-to-backplane, 500 VDC field-to-chassis\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eInput Impedance\u003c\/td\u003e\n\u003ctd\u003eGreater than 10 Mohms (Voltage\/TC\/RTD), Less than 250 ohms (Current)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003c\/figure\u003e\n\u003ch3\u003eFitur Kontrol \u0026amp; Drive Industri\u003c\/h3\u003e\n\u003cp\u003eInfrastruktur pemrosesan sinyal universal berinteraksi dengan kerangka kerja komunikasi bus backplane standar untuk memastikan pemetaan variabel berkapasitas tinggi di seluruh sistem chassis lokal. Beroperasi dalam jaringan deterministik Profinet \/ EtherNet\/IP yang dikendalikan oleh CPU master, modul ini menetapkan profil konfigurasi individu per titik terminal, memperluas opsi skala kepadatan I\/O dasar dalam satu jejak perangkat keras. Konfigurasi saluran, pengaturan filter, dan metrik kalibrasi sensor sesuai dengan standar kompatibilitas firmware flash asli, memungkinkan deteksi sirkuit terbuka waktu nyata dan diagnostik batas untuk melaporkan langsung ke tabel data pengontrol.\u003c\/p\u003e\n\u003ch3\u003ePertanyaan yang Sering Diajukan\u003c\/h3\u003e\n\u003cp\u003eQ: Bagaimana rating isolasi listrik saluran-ke-saluran pada 1769sc-IF8U?\u003c\/p\u003e\n\u003cp\u003eA: Modul menyediakan penghalang pemisah internal dengan isolasi saluran-ke-saluran 10 VDC, disertai dengan rating perlindungan dielektrik 500 VDC yang lebih tinggi antara kabel sisi lapangan dan komponen logika backplane.\u003c\/p\u003e\n\u003cp\u003eQ: Apakah modul universal ini mendukung hot-swapping atau pelepasan saat daya listrik aktif?\u003c\/p\u003e\n\u003cp\u003eA: Tidak, mekanika platform 1769 tidak secara asli mendukung pemasangan dan pelepasan online (RIUP). Daya backplane sistem harus sepenuhnya diisolasi sebelum melepas unit untuk menghindari kerusakan memori eksekusi.\u003c\/p\u003e\n\u003cp\u003eQ: Apakah 1769sc-IF8U dapat memindai semua delapan saluran secara bersamaan saat dicampur dengan termokopel dan loop 4-20 mA?\u003c\/p\u003e\n\u003cp\u003eA: Ya, perangkat keras konversi onboard secara dinamis mengurutkan saluran yang diaktifkan berdasarkan parameter frekuensi filter data yang ditetapkan (berkisar dari 5 Hz hingga 1000 Hz) yang ditentukan melalui parameter RSLogix 5000.\u003c\/p\u003e\n\u003ch3\u003ePedoman Pemasangan Lapangan\u003c\/h3\u003e\n\u003cp\u003eIsolasikan catu daya backplane chassis utama 1769 dan pastikan sistem benar-benar tidak berenergi sebelum memulai pemasangan. Selaraskan jalur lidah dan alur modul dengan hati-hati pada slot perangkat keras yang berdekatan dan pasang rakitan pada rel DIN 35 mm atau kisi panel. Aktifkan mekanisme tuas bus terintegrasi untuk menutup pin sirkuit backplane dengan kuat. Patuhi batas jarak maksimum catu daya sebanyak 8 modul dari kartu sumber daya. Akhiri semua kabel sensor menggunakan konduktor twisted-pair terlindung kapasitansi rendah (STP) yang ditentukan, dengan menjaga pemisahan fisik antara kabel sinyal tegangan rendah dan kabel daya tegangan tinggi. Tanamkan pelindung anyaman tembaga secara keseluruhan pada satu titik tanah utama impedansi rendah di dalam panel kabinet, memastikan pelindung sensor tidak ditanahkan di kedua ujung untuk mencegah terbentuknya loop tanah pada sirkuit pengukuran 16-bit.\u003c\/p\u003e","brand":"Allen Bradley","offers":[{"title":"Default Title","offer_id":44427615076451,"sku":"1769sc-IF8u","price":310.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0583\/5246\/8067\/files\/240._ca94e96c-c98b-431b-b3cc-cdbb3f907f58.jpg?v=1785483165","url":"https:\/\/www.autocontrolglobal.com\/id\/products\/allen-bradley-1769sc-if8u-8-channel-universal-analog-module","provider":"AutoControl Global","version":"1.0","type":"link"}