KL3032X1-BA1 Analog Input CHARM | Emerson DeltaV CHARMs
Manufacturer: Emerson
-
Part Number: SE4303T02 KL3032X1-BA1
Condition:New with Original Package
Product Type: Analog Input CHARM
-
Country of Origin: USA
Payment:T/T, Western Union
Shipping port: Xiamen
Warranty: 12 months
Product Description
Product Overview
The Emerson DeltaV KL3032X1-BA1, also referenced as SE4303T02, is a 24 VDC powered Analog Input CHARM designed for flexible current signal measurement in DeltaV CHARMs I/O systems.
This CHARM supports 4–20 mA and 0–20 mA signals, enabling direct connection of modern field transmitters without additional interface modules.
Moreover, the module supports 2-wire, 3-wire, and 4-wire devices, simplifying field wiring while reducing engineering complexity.
Therefore, it plays a critical role in electronic marshalling strategies where late-stage I/O changes are expected.
As part of Emerson’s CHARMs architecture, the KL3032X1-BA1 delivers hot-swappable installation, automatic configuration, and consistent performance across wide environmental conditions.
Technical Specifications
Product Type: Analog Input CHARM
Model / Order Code: KL3032X1-BA1
CHARM Identifier: SE4303T02
Manufacturer: Emerson
System Compatibility: DeltaV™ CHARMs Electronic Marshalling
Supported Signal Types:
-
4–20 mA with or without HART
-
0–20 mA optional
Nominal Signal Range: 4–20 mA
Full Signal Range: 0 to 24 mA
Supported Field Devices:
-
2-wire loop-powered transmitters
-
3-wire devices powered through CHARM
-
4-wire externally powered devices
Field Power (2-wire): 15.0 V at 20 mA with 24 V DC input
Input Impedance: 250 Ω ±1%
Accuracy:
-
±0.1% of span from 0 to 60 °C
-
±0.25% of span from –40 to +70 °C
Repeatability: 0.05% of span
Resolution: 16-bit A/D converter
Calibration: None required
Field Circuit Protection: 30 mA current limiting and wiring disconnect
CHARM Power Requirement:
-
36 mA max at 24 V DC for 2-wire devices
-
12 mA max at 24 V DC for 3-wire and 4-wire devices
Heat Dissipation: 0.33 W
HART Support:
-
HART v7 pass-through for AMS
-
HART variables and device status available for control
HART Update Rate: Faster than one second, depending on device and network loading
Operating Temperature: –40 °C to +70 °C
Mounting Method: DeltaV CHARM I/O Carrier
Installation: Hot-swappable during system operation
Lifecycle Status: Active and fully supported by Emerson
Frequently Asked Questions
Q1: What signal types does KL3032X1-BA1 support?
A1: It supports 4–20 mA and optional 0–20 mA current signals, with or without HART.
Q2: Can this CHARM power field transmitters directly?
A2: Yes, it provides loop power for 2-wire devices and supports 3-wire and 4-wire configurations.
Q3: Is HART communication supported?
A3: Yes, HART v7 pass-through is supported for AMS diagnostics and control variables.
Q4: Does the module require calibration?
A4: No, the KL3032X1-BA1 is factory calibrated and requires no user calibration.
Q5: Can the CHARM be replaced while the system is running?
A5: Yes, it supports hot-swap installation in DeltaV CHARMs I/O carriers.