Yokogawa AAI135-S03/K4A00 Analog Input Module – Product Description
Overview
The Yokogawa AAI135-S03/K4A00 is a high-performance analog input module designed for precise measurement in CENTUM VP and ProSafe‑RS systems. Moreover, its compact rack-mounted design allows for high channel density while maintaining excellent reliability in mission-critical industrial environments.
Technical Specifications
Electrical & I/O
-
Number of Channels: 16 analog input channels
-
Signal Types Supported: 4–20 mA DC current input, 1–5 V DC voltage input
-
Resolution: 16-bit A/D conversion
-
Accuracy: ±0.1% of full scale (typical)
-
Input Impedance: Current mode 250 Ω, Voltage mode ≥1 MΩ
-
Isolation: Channel-to-channel and channel-to-system
-
Power Supply: 24 V DC via system backplane
Performance
-
Response Time: ≤10 ms per channel
-
Noise Immunity: High resistance to electrical noise and EMI
-
Diagnostics: LED indicators for module status, built-in self-test, fault detection
-
Reliability: Continuous 24/7 operation
-
Redundancy: Supports dual redundant configuration
Mechanical
-
Mounting: Rack-mounted in Yokogawa system backplane
-
Dimensions (W × H × D): 130 × 130 × 32 mm
-
Weight: 0.5 kg
-
Cooling: Natural convection
-
Protection: IP20
Communication & Integration
-
Interface: Proprietary Yokogawa ESB bus
-
Compatibility: CENTUM VP DCS and ProSafe‑RS SIS
-
Configuration: Managed via Yokogawa engineering tools
Environmental & Compliance
-
Operating Temperature: 0 °C to +55 °C
-
Storage Temperature: −20 °C to +70 °C
-
Relative Humidity: 5–95% non-condensing
-
Certifications: CE, UL, CSA, IEC 61508 SIL2
-
Origin: Manufactured in Japan
FAQ
Q1: How many analog channels does this module support?
It provides 16 analog input channels for current and voltage signals.
Q2: What is the input voltage and current range?
4–20 mA for current inputs and 1–5 V for voltage inputs.
Q3: Can it operate continuously in critical systems?
Yes, it is designed for 24/7 operation in mission-critical environments.
Q4: Does it support redundancy for reliability?
Yes, dual redundant configuration is supported.
Q5: How can I monitor module status?
LED indicators display channel and module status along with fault conditions.