ProSoft MVI46-MCM Modbus RTU/ASCII Master Slave Module
Manufacturer: Allen Bradley
-
Part Number: MV146-MCM
Condition:New with Original Package
Product Type: Modbus Communication Module
-
Country of Origin: USA
Payment:T/T, Western Union
Shipping port: Xiamen
Warranty: 12 months
ProSoft MVI46-MCM SLC 500 Modbus Master/Slave Network Interface Module
Product Overview
The ProSoft MVI46-MCM (MV146-MCM) is a specialized Modbus communication interface designed for Allen-Bradley SLC 500 series PLCs. Functioning as a high-performance bridge, this single-slot module allows SLC processors to communicate seamlessly with Modbus RTU and ASCII devices. Whether acting as a Modbus Master or Slave, the MVI46-MCM handles complex data transfers independently of the PLC processor, ensuring that network traffic does not degrade the controller's scan time. It is an essential component for integrating third-party hardware—such as power meters, variable frequency drives (VFDs), and flow controllers—into a Rockwell Automation environment.
Industrial Application Scenarios
-
Energy Management: Collecting real-time power consumption data from Modbus-enabled digital power meters.
-
Process Automation: Interfacing with chemical analyzers and temperature controllers in pharmaceutical or food processing.
-
HVAC & Building Control: Integrating boiler and chiller controllers into an SLC-based central monitoring system.
-
SCADA Integration: Functioning as a Modbus Slave to provide SLC data to a higher-level Master SCADA system.
Technical Specifications
The following technical parameters detail the hardware and communication capabilities of the MVI46-MCM:
| Parameter | Specification Details |
| Model Number | MVI46-MCM / MV146-MCM |
| Manufacturer | ProSoft Technology (inRAx Series) |
| Compatibility | Allen-Bradley SLC 5/02, 5/03, 5/04, 5/05 (M0/M1 Capable) |
| Backplane Current | 800 mA @ 5.1 V DC |
| Protocols | Modbus RTU and Modbus ASCII |
| Application Ports | Two (2) RJ45 (RS-232/422/485 configurable) |
| Configuration Port | One (1) RJ45 RS-232 (Configuration/Debug) |
| Baud Rates | 110 bps to 115.2 kbps |
| Max Registers | 5000 User Database Registers |
| Max Commands | 100 Commands per Port |
| Operating Temp | 0 °C to 60 °C (32 °F to 140 °F) |
| Form Factor | Single-slot 1746 Chassis Module |
| Isolation | Optical Isolation between Backplane and Network |