140DAI54000 | Schneider Modicon Quantum Input Module
Manufacturer: Schneider
-
Part Number: 140DAI54000
Condition:New with Original Package
Product Type: AC Discrete Input Modules
-
Country of Origin: France
Payment:T/T, Western Union
Shipping port: Xiamen
Warranty: 12 months
Schneider Electric 140DAI54000 Modicon Quantum AC Discrete Input Module
The 140DAI54000 is a 16-channel AC discrete input module for the Modicon Quantum PLC platform. It acquires 115 V AC field signals across 47–63 Hz with 1780 Vrms channel-to-channel and channel-to-bus isolation for 1 minute, providing 16 green input LEDs, an active LED, a fault LED, and support for Concept, ProWORX 32, and Unity Pro.
Input Thresholds and Electrical Characteristics
Logic state thresholds and impedance vary slightly with line frequency across the 47–63 Hz operating range. Logic 1 requires 79–132 V AC at 57–63 Hz or 85–132 V AC at 47–53 Hz, while logic 0 spans 0–20 V AC, and input current and impedance shift accordingly between 57–63 Hz and 47–53 Hz.
The module tolerates up to 132 V AC continuous input, 156 V AC for 10 seconds, and 200 V AC for 1 cycle, with a maximum leakage current limit of 2.1 mA. OFF-to-ON response takes 0.75–4.9 line cycles and ON-to-OFF response takes 7.3–12.3 ms, while bus draw is 180 mA and maximum power dissipation is 5.5 W.
Conflict Note on Addressing Requirement
The supplied bullet summary lists an addressing requirement of 2 input words, whereas the technical specification table lists 1 input word. Confirm the exact word allocation in your project configuration before assigning I/O addresses.
Technical Specifications
| Parameter | Specification |
|---|---|
| Model | 140DAI54000 |
| Brand | Schneider Electric |
| Product Series | Modicon Quantum |
| Product Type | AC Discrete Input Module |
| Number of Inputs | 16 |
| Input Type | AC Digital Input |
| Rated Input Voltage | 115 V AC |
| Input Frequency | 47–63 Hz |
| Input Current | 11.1 mA at 57–63 Hz; 13.2 mA at 47–53 Hz |
| Logic State 1 | 79–132 V AC at 57–63 Hz; 85–132 V AC at 47–53 Hz |
| Logic State 0 | 0–20 V AC |
| Input Impedance | 12 kohm at 57–63 Hz; 14.4 kohm at 47–53 Hz |
| Maximum Leakage Current | 2.1 mA |
| Maximum Continuous Input | 132 V AC |
| Maximum Input (10 seconds) | 156 V AC |
| Maximum Input (1 cycle) | 200 V AC |
| Response Time (OFF to ON) | 0.75–4.9 line cycles |
| Response Time (ON to OFF) | 7.3–12.3 ms |
| Channel Isolation | 1780 Vrms for 1 minute |
| Channel-to-Bus Isolation | 1780 Vrms for 1 minute |
| Bus Current Consumption | 180 mA |
| Maximum Power Dissipation | 5.5 W |
| Status Indicators | 16 Green Input LEDs, 1 Green Active LED, 1 Red Fault LED |
| Compatible Software | Concept, ProWORX 32, Unity Pro |
| Mounting | Modicon Quantum PLC Rack |
| Module Format | Standard |
| Net Weight | 0.31 kg |
Frequently Asked Questions
Q: What input voltage ranges define Logic 1 and Logic 0 on the 140DAI54000? A: Logic 0 is 0–20 V AC. Logic 1 is 79–132 V AC at 57–63 Hz and 85–132 V AC at 47–53 Hz.
Q: What is the maximum allowed input voltage and leakage current on the 140DAI54000? A: Continuous input must not exceed 132 V AC, with short-term limits of 156 V AC for 10 seconds and 200 V AC for 1 cycle. Maximum leakage current is 2.1 mA.