Schneider Electric 140DRA84000 Modicon Quantum Discrete Relay Output Module
The 140DRA84000 is a 16-channel discrete relay output module for the Modicon Quantum PLC platform. Each channel provides an independent electromechanical relay with a normally open Form A contact to switch AC and DC field loads, supporting 20–250 V AC and 5–150 V DC circuits with galvanic isolation via relay contacts and green LED status indicators.
Switching and Load Capabilities
Each output switches up to 2 A per point for resistive loads at 60 deg C, with a maximum surge current of 10 A for 10 ms and a resistive switching capacity of 500 VA. Inductive loads and tungsten lamp loads are rated up to 1 A, while a minimum load current of 50 mA applies to reliable switching.
DC switching covers 5–30 V DC as a standard DC range and extends from 30–150 V DC at reduced current, including 300 mA resistive for 30–50 V DC loads. Because mechanical durability is rated at 10 million operations while electrical durability depends on load characteristics, switching heavy inductive or high-inrush loads reduces contact life faster than light resistive loads.
System Integration and Field Wiring
The module occupies one output word in the Modicon Quantum addressing space and mounts in a standard Modicon Quantum rack. Individual green LEDs indicate output status, and a removable field wiring terminal arrangement supports field connection and module replacement.
Technical Specifications
| Parameter | Specification |
|---|---|
| Model | 140DRA84000 |
| Brand | Schneider Electric |
| Product Series | Modicon Quantum |
| Product Type | Discrete Relay Output Module |
| Number of Outputs | 16 |
| Output Type | Electromechanical Relay |
| Contact Configuration | 1 NO per channel |
| Contact Form | Form A |
| Output Voltage (AC) | 20–250 V AC |
| Output Voltage (DC) | 5–30 V DC |
| Extended DC Voltage | 30–150 V DC (reduced current) |
| Maximum Load Current | 2 A per point (resistive, at 60 deg C) |
| Tungsten Lamp Load | 1 A |
| Inductive Load | 1 A |
| DC Load (30–50 V) | 300 mA resistive |
| Minimum Load Current | 50 mA |
| Maximum Surge Current | 10 A for 10 ms |
| Switching Capacity | 500 VA resistive |
| OFF-to-ON Response | 10 ms maximum |
| ON-to-OFF Response | 20 ms maximum |
| Mechanical Durability | 10 million operations |
| Electrical Durability | Load-dependent |
| Addressing Requirement | 1 output word |
| Status Indicators | Green LEDs |
| Mounting | Modicon Quantum rack |
| Module Format | Standard |
| Dimensions | 2.0 in x 10.0 in x 4.0 in (5.1 cm x 25.4 cm x 10.2 cm) |
| Weight | 1 lbs 5.0 oz (0.6 kg) |
| Country of Manufacture | France |
| Tariff Code | 8538907080 |
Frequently Asked Questions
Q: What is the maximum current rating per output channel on the 140DRA84000? A: It is rated for a maximum of 2 A per point for resistive loads at 60 deg C, with a 1 A limit for tungsten lamp and inductive loads. High-voltage DC loads above 30 V DC require reduced current, such as 300 mA resistive for 30–50 V DC.
Q: How many PLC address words does the 140DRA84000 use? A: It requires 1 output word to address its 16 discrete relay output channels within a Modicon Quantum rack.