16-Channel Analog Voltage Input Module IC693ALG222E GE Series 90-30
16-Channel Analog Voltage Input Module IC693ALG222E GE Series 90-30
16-Channel Analog Voltage Input Module IC693ALG222E GE Series 90-30
/ 3

16-Channel Analog Voltage Input Module IC693ALG222E GE Series 90-30

  • Manufacturer: GE Fanuc

  • Part Number: IC693ALG222E

  • Condition:New with Original Package

  • Product Type: Analog Input Modules

  • Country of Origin: USA

  • Payment:T/T, Western Union

  • Shipping port: Xiamen

  • Warranty: 12 months

GE Fanuc IC693ALG222E Series 90-30 Analog Input Module

Configured for analog signal conversion in Series 90-30 PLC systems, the GE Fanuc IC693ALG222E (IC693ALG222 analog voltage input module) provides direct physical/electrical execution. It converts field voltage signals into digital data across 16 single-ended or 8 differential channels for central processing.

Hardware Specifications

Parameter Specification
Model IC693ALG222E
Brand GE Fanuc
Origin United States
Weight 0.36 kg
Dimensions 36 x 130 x 135 mm
Operating Temp 0 to 60 deg C
Power Consumption 112 mA max at 5 VDC, 41 mA max at 24 VDC
Channel Capacity 16 single-ended or 8 differential channels
Input Voltage Range 0 to 10 VDC (unipolar), -10 to +10 VDC (bipolar)
Resolution 2.5 mV/count (unipolar), 5 mV/count (bipolar)
Update Rate 6 ms (16 single-ended), 3 ms (8 differential)
Accuracy +/-0.25% full scale at 25 deg C
Isolation 1500 VAC field-to-logic (1 min), 250 VAC continuous

Backplane Bus & Deterministic Data Ingestion

The IC693ALG222E interfaces directly with the Series 90-30 backplane bus to deliver updated digital representations of analog voltage inputs to CPU memory racks. Backplane communication velocity enables rapid refresh cycles, updating 16 single-ended channels within 6 ms or 8 differential channels within 3 ms. Internal firmware flash compatibility and high I/O density scaling allow reliable signal processing across baseplates while preserving deterministic bus communication.

Frequently Asked Questions

Q: How does switching between single-ended and differential wiring modes impact module scan updates?

A: Configuring the module for 8 differential channels reduces the scan update time to 3 ms, whereas utilizing all 16 single-ended channels requires 6 ms to process all inputs across the backplane bus.

Q: What are the dual backplane power supply draw specifications for this module?

A: The IC693ALG222E draws up to 112 mA from the +5 VDC logic bus rail alongside 41 mA maximum from the isolated +24 VDC supply rail.

Q: What level of electrical isolation protects host PLCs from field voltage surges?

A: Optical isolation provides 1500 VAC protection for one minute between field wiring terminals and the backplane logic bus, preventing high-voltage transients from reaching internal system components.

Field Installation Guidelines

Mount the IC693ALG222E into any available I/O slot of a Series 90-30 baseplate after turning off backplane power. Connect analog field wiring using shielded twisted-pair cables to prevent electro-magnetic noise coupling. Land cable shields at a single chassis ground point near the rack entry. Maintain a physical separation of at least 300 mm between low-voltage analog signal lines and AC power cables. Verify that ambient temperature around the enclosure remains within 0 to 60 deg C to ensure accurate analog conversion across all channels.