16-Channel Thermocouple Input Module | GE Fanuc HE693THM166
Manufacturer: GE Fanuc
-
Part Number: HE693THM166
Condition:New with Original Package
Product Type: Thermocouple Input Modules
-
Country of Origin: USA
Payment:T/T, Western Union
Shipping port: Xiamen
Warranty: 12 months
GE Fanuc HE693THM166 Thermocouple Input Module
The GE Fanuc HE693THM166 is a high-density 16-channel thermocouple input module manufactured by Horner Automation for GE Fanuc Series 90-30 PLC systems. It provides direct interfacing between thermocouple sensors and the PLC backplane without external signal converters, enabling precise multi-point temperature acquisition for industrial process monitoring.
Signal Processing and Thermocouple Support
The module features 16 isolated thermocouple input channels supporting sensor types J, K, N, T, E, R, S, B, C, and X. Utilizing an integrating A/D conversion method with a rate of 40 channels per second, the module delivers a temperature resolution of 0.5 deg C (or 0.5 deg F) and a typical accuracy of ±0.5 deg C for standard J, K, N, and T types. Integrated open-circuit detection automatically identifies broken field sensor wires and reports fault alarms to the system controller.
System Integration and PLC Memory Mapping
Designed for Series 90-30 I/O rack mounting, the module maps field data into the PLC using 16 analog input words (%AI) and 16 discrete input bits (%I). Field wiring connects via a 32-position removable terminal block using recommended 24 AWG wire. Power is drawn directly from the backplane, consuming 100 mA at 5 VDC.
| Parameter | Specification |
|---|---|
| Model Number | HE693THM166 |
| Brand | GE Fanuc |
| Product Series | Series 90-30 |
| Product Type | High-Density Thermocouple Input Module |
| Number of Channels | 16 points |
| Supported Thermocouple Types | J, K, N, T, E, R, S, B, C, X |
| Temperature Resolution | 0.5 deg C (0.5 deg F) |
| Typical Accuracy | ±0.5 deg C (for J, K, N, T types) |
| Input Impedance | 20 Mohm |
| Maximum Safe Overload | ±35 V |
| Common-Mode Voltage Range | ±12 V |
| Common-Mode Rejection | > 100 dB |
| Conversion Rate | 40 channels / second |
| Backplane Power Consumption | 100 mA at 5 VDC |
| Field Wiring Connector | 32-position removable terminal block |
| Weight | 0.70 lbs |
| Operating Temperature | 0 deg C to +60 deg C |
Frequently Asked Questions
Q: What PLC platform is compatible with the HE693THM166 module? A: The HE693THM166 is designed for installation in standard GE Fanuc Series 90-30 PLC I/O racks.
Q: How does the HE693THM166 handle open or damaged thermocouple sensors? A: The module includes built-in open-circuit detection that detects broken sensor wiring and triggers an open-circuit alarm bit within the PLC status register.
Q: How much backplane current does this thermocouple module draw? A: It draws 100 mA at 5 VDC from the Series 90-30 PLC backplane power supply.