16-Point Discrete Input Module GE IC200MDL243D VersaMax 120 VAC
Manufacturer: GE Fanuc
-
Part Number: IC200MDL243D
Condition:New with Original Package
Product Type: Digital I/O Cards
-
Country of Origin: USA
Payment:T/T, Western Union
Shipping port: Xiamen
Warranty: 12 months
GE Fanuc IC200MDL243D VersaMax Discrete Input Module
The GE Fanuc IC200MDL243D, also cataloged as the IC200MDL243 Discrete Input Module, operates as a dedicated hardware component for AC voltage signal acquisition within VersaMax I/O and Control System platforms.
Hardware Specifications
| Parameter | Specification |
|---|---|
| Model | IC200MDL243D |
| Brand | GE Fanuc |
| Origin | United States |
| Weight | 0.20 kg (0.44 lbs) |
| Dimensions | 110 mm x 66.8 mm x 50.0 mm |
| Operating Temp | 0 to +60 deg C |
| Power Consumption | 100 mA at 5 VDC |
| Operating Voltage | 120 VAC |
| Number of Inputs | 16 Discrete Inputs |
| Maximum Response Time (On) | 1 Cycle |
| Channel Isolation | Yes (Field to backplane logic) |
| Status Indicators | 16 individually numbered input LEDs, 1 backplane status LED |
Backplane Bus Communication Velocity & I/O Density Scaling
The module routes discrete AC status signals directly to the VersaMax CPU across the carrier backplane interface, utilizing high-density scaling to process 16 discrete channels within a compact physical footprint. Operating with a 100 mA backplane current load at 5 VDC, the unit executes 120 VAC discrete state detection with a maximum response time of 1 cycle. Channel isolation shields backplane bus communication velocity from field-side electrical noise, voltage transients, and ground potential differences across the I/O network.
Frequently Asked Questions
Q: How does the IC200MDL243D mount onto the VersaMax I/O rack structure?
A: The module snaps directly onto a standard VersaMax I/O carrier, interfacing with the backplane bus and field wiring terminal strip without requiring additional ribbon cables.
Q: What diagnostic indicators are integrated into the front faceplate of the module?
A: The front panel includes 16 individually numbered green LEDs indicating the ON/OFF state of each 120 VAC input channel, along with 1 backplane status LED for power and communication monitoring.
Q: Can the IC200MDL243D be removed from the carrier while backplane power is active?
A: Field installation practices require isolating system power and field voltage sources prior to insertion or removal to prevent electrical arcing across the carrier connectors.
Field Installation Guidelines
Ensure main control cabinet power and field-side 120 VAC voltage sources are fully de-energized before mounting the module onto its I/O carrier. Align the module side guides with the carrier slot and press firmly until the locking mechanism fully engages. Wire field input conductors to the designated terminal block positions, maintaining proper routing and separation between AC signal lines and low-voltage DC communication wiring. Connect cabinet frame ground to the carrier DIN rail to ensure effective shield grounding and surge protection.