170AAI14000 | Schneider | Modicon Momentum Analog Input Module
170AAI14000 | Schneider | Modicon Momentum Analog Input Module
170AAI14000 | Schneider | Modicon Momentum Analog Input Module
/ 3

170AAI14000 | Schneider | Modicon Momentum Analog Input Module

  • Manufacturer: Schneider

  • Part Number: 170AAI14000

  • Condition:New with Original Package

  • Product Type: Modicon Momentum Analog Input Module

  • Country of Origin: USA

  • Payment:T/T, Western Union

  • Shipping port: Xiamen

  • Warranty: 12 months

Product Description

The Schneider Electric 170AAI14000 is a distributed analog input module designed for the Modicon Momentum platform. It provides 16 high-precision input channels, capable of processing voltage signals (±10 V, ±5 V) and current signals (4–20 mA), making it ideal for industrial measurement and control applications.

This compact module features full 16-bit signed data resolution, robust channel-to-bus isolation, and internal protection against reverse polarity and overcurrent conditions. Sixteen LEDs indicate channel status, enabling rapid diagnostics and maintenance. Removable terminal blocks simplify wiring, while low-pass filtering ensures signal integrity.

The 170AAI14000 integrates seamlessly with Momentum CPUs and communication adapters, supporting accurate data acquisition from field devices such as temperature transmitters, flow meters, and pressure sensors. Its rugged design allows operation in demanding environments, with compliance to CE, CSA, FM Class 1 Division 2, and UL standards.

Purpose: Converts analog signals from field devices into precise digital values for PLC processing.

Applications: Process automation, material handling, energy management, and simple machine control.

Technical Specifications

Parameter Details
Model 170AAI14000
Series Modicon Momentum
Type Distributed Analog Input Module
Number of Channels 16 single-ended analog inputs
Input Ranges ±10 V, ±5 V, 4–20 mA
Resolution 12-bit converted to 16-bit signed
Accuracy @25 °C ±0.15% FS (±10 V), ±0.25% FS (±5 V, 4–20 mA)
Accuracy @60 °C ±0.25% FS (±10 V), ±0.45% FS (±5 V), ±0.25% FS (4–20 mA)
Input Impedance >2200 kΩ (voltage), <0.25 Ω (current)
Filter 10 kHz low-pass
Temperature Drift 30 ppm FS/°C
Isolation 1780 V AC channel-to-ground, 500 V AC supply-to-ground
Electrical Connection 2 removable terminal blocks
Protection Internal 2 A slow-blow, 500 mA fast-blow
Local Signalling 16 LEDs channel status
Dimensions 141.5 × 125 × 47.5 mm
Weight 0.215 kg (0.474 lb)
Mounting Wall or panel mount
Compliance CE, UL, CSA, FM Class 1 Division 2
Operating Temperature 0–60 °C
Storage Temperature –40–85 °C

 