6-Point Fast Analog Module | Allen-Bradley 1769-IF4FXOF2F
6-Point Fast Analog Module | Allen-Bradley 1769-IF4FXOF2F
6-Point Fast Analog Module | Allen-Bradley 1769-IF4FXOF2F
/ 3

6-Point Fast Analog Module | Allen-Bradley 1769-IF4FXOF2F

  • Manufacturer: Allen Bradley

  • Part Number: 1769-IF4FXOF2F

  • Condition:New with Original Package

  • Product Type: Analog I/O Modules

  • Country of Origin: USA

  • Payment:T/T, Western Union

  • Shipping port: Xiamen

  • Warranty: 12 months

Allen-Bradley 1769-IF4FXOF2F Compact I/O Analog Combination Module

Configured for high-speed signal processing in CompactLogix and MicroLogix 1500 architectures, the Allen-Bradley 1769-IF4FXOF2F (1769-IF4FXOF2F Analog Combination Module) provides direct physical/electrical execution. The hardware framework interfaces four single-ended or differential analog input channels and two single-ended analog output channels directly with the central processing unit via a Delta-Sigma converter architecture. Operating within an open-style chassis configuration that permits both DIN-rail and panel mounting, the device translates industrial voltage and current signals using a high-speed 1 ms conversion rate across a 30 VAC/DC reinforced isolation barrier.

Hardware Specifications

Parameter Specification
Model 1769-IF4FXOF2F
Brand Allen-Bradley
Origin USA
Weight 0.43 kg (0.94 lbs)
Dimensions Single-slot module width
Operating Temp 0 to +60 deg C
Power Consumption 33.6 W
Power Dissipation 7.5 W
Backplane Current 90 mA at 5.1 VDC / 1.4 A at 24 VDC
Power Supply Distance Rating 8 modules
Analog Inputs 4 channels (single-ended or differential)
Analog Outputs 2 channels (single-ended)
Input Ranges ±10.5 V, -0.5 to 10.5 V, -0.5 to 5.25 V, 0.5 to 5.25 V, 0 to 21 mA, 3.2 to 21 mA
Output Ranges ±10.5 V, -0.5 to 10.5 V, -0.5 to 5.25 V, 0.5 to 5.25 V, 0 to 21 mA, 3.2 to 21 mA
Input Resolution 14 to 15 bits
Output Resolution 13 to 14 bits
Step Response 2 ms to 63%
Filter Frequencies Selectable: 5 Hz, 10 Hz, 50 Hz, 60 Hz, 100 Hz, 250 Hz, 500 Hz, 1000 Hz
Isolation Voltage 30 V AC/DC continuous, IEC Class 2 reinforced

Industrial Control & Drive Features

The physical interface operates inside standard backplane bus communication velocity frameworks, allowing low-latency updates directly to the controller tags. Configured channels support mixed-signal installations across Profinet / EtherNet/IP deterministic networks by executing independent voltage or current signal calibration per terminal point. The physical scaling parameters are maintained natively within the device registers, providing over-range and under-range fault detection without adding burden to the controller loop. This dense I/O density scaling aligns with existing 1769 modules, maintaining firmware flash compatibility across standard automation architectures.

Frequently Asked Questions

Q: What is the maximum current load drawn from the backplane by the 1769-IF4FXOF2F?

A: The module demands 90 mA at 5.1 VDC and 1.4 A at 24 VDC from the system backplane power supply, which must be factored into the overall chassis power budget.

Q: Can the input channels be mixed between current loops and voltage signals simultaneously?

A: Yes, each of the four input points is individually configurable through the software matrix to accept independent ranges including 4-20 mA, 0-20 mA, ±10 V, or 1-5 V.

Q: Does this high-speed module support hot-swapping under active chassis power?

A: No, the 1769 platform architecture requires the system backplane to be entirely de-energized before removing or inserting modules to prevent internal circuit damage.

Field Installation Guidelines

Ensure that the main electrical power feed to the Compact I/O bank is disconnected before mounting the module. Position the unit onto the 35 mm DIN rail or panel surface, using the built-in interlocking tongue-and-groove guides to achieve exact mechanical alignment with the adjacent module. Slide the integrated bus lever to the locked position to complete the internal backplane electrical connection. Maintain a strict power supply distance rating of no more than 8 modules from the system power source. Connect all field wiring using recommended shielded twisted-pair (STP) cable categorized for analog signals, routing the lines away from high-voltage conduit or motor drive lines. Terminate the overall cable shields at a single, clean ground terminal point inside the enclosure to eliminate electrical noise interference across the analog channels.