8 Channel Analog Input Module GE IC200ALG260A
8 Channel Analog Input Module GE IC200ALG260A
8 Channel Analog Input Module GE IC200ALG260A
/ 3

8 Channel Analog Input Module GE IC200ALG260A

  • Manufacturer: GE Fanuc

  • Part Number: IC200ALG260A

  • Condition:New with Original Package

  • Product Type: Analog Input Modules

  • Country of Origin: USA

  • Payment:T/T, Western Union

  • Shipping port: Xiamen

  • Warranty: 12 months

GE Fanuc IC200ALG260A VersaMax Analog Input Module

Configured for multi-channel signal acquisition in VersaMax PLC platforms, the GE Fanuc IC200ALG260A (IC200ALG260 Analog Input Module) provides direct physical/electrical execution. The module digitizes analog voltage and current signals into 12-bit binary representations for real-time CPU scan execution.

Hardware Specifications

Parameter Specification
Model IC200ALG260A
Brand GE Fanuc / Emerson
Origin Refer to device label
Weight 0.26 kg (0.56 lbs)
Dimensions 120 mm x 90 mm x 40 mm
Operating Temp 0 deg C to +60 deg C
Power Consumption 125 mA @ 5 VDC (backplane current consumption)
Channel Count 8 single-ended analog input channels
Signal Range (Voltage) +/-10 VDC unipolar or bipolar
Signal Range (Current) 4-20 mA DC
Resolution 12-bit
Input Impedance Voltage: >=100 k-ohm, Current: 250 ohm
Isolation Optical isolation: 250 VAC continuous, 1500 VAC for 1 minute
Update Rate 0.4 ms
Filter Response Time 5.0 ms
LED Indicators 2 status LEDs ("OK" and "INT PWR")

Backplane Bus Communication Velocity & Network Execution

The module interfaces with the VersaMax carrier backplane to process high-speed analog updates at a scan rate of 0.4 ms. System integration drivers maintain deterministic backplane bus communication velocity while preventing network latency across local and expansion racks. Internal firmware flash compatibility enables configured filter response times down to 5.0 ms, providing fast signal conditioning without sacrificing optical isolation integrity between field circuits and system logic.

Frequently Asked Questions

Q: How does the module react if an internal logic fault or power loss occurs?

A: Integrated diagnostics detect internal power failure or module error conditions. The channel logic can be configured via software parameters to hold the last valid analog state or default to a pre-defined value.

Q: What power rail supplies the analog input module logic?

A: The module draws its operational logic power directly from the 5 VDC backplane bus, consuming up to 125 mA during active scanning.

Q: What physical optical isolation levels exist between field wiring and the system backplane?

A: Optical isolation barriers protect backplane logic by supporting 250 VAC continuous isolation and withstand ratings up to 1500 VAC for 1 minute.

Field Installation Guidelines

  • Mount the module securely onto a standard 35 mm DIN rail or flat enclosure panel using a compatible VersaMax carrier baseplate.
  • Wire all 4-20 mA current loops and +/-10 VDC voltage connections using shielded twisted-pair cables. Separate signal cable paths from AC power lines and motor leads.
  • Terminate all cable shield drain wires at a single grounding point on the enclosure ground bar to prevent noise pickup and ground loops.
  • Ensure cabinet ventilation maintains ambient operating temperatures between 0 deg C and +60 deg C with non-condensing relative humidity below 95%.