GE Fanuc 8104-AO-IP 8-Channel Analog Output Module – Product Description
Product Summary
The GE Fanuc 8104-AO-IP is an 8-channel analog output module from the PAC8000 series, designed for precise current-loop signal control in industrial automation. Each channel delivers 4–20 mA output, with 12-bit resolution and built-in open circuit detection. Moreover, the module supports fail-safe operation and configurable initialization states, ensuring reliable performance even in critical process applications. Its compact, carrier-mounted design allows flexible DIN-rail or flat-surface mounting, making it suitable for both new installations and upgrades. The rugged industrial build supports operation in hazardous areas, offering dependable service in demanding environments.
Technical Specifications
General Information
-
Manufacturer: GE / MTL (PAC8000 series)
-
Model Number: 8104-AO-IP
-
Product Type: 8-Channel Analog Output Module
-
Weight: .5 kg
-
Compact carrier-mounted design
-
DIN-rail or flat-surface mounting
Outputs
-
8 single-ended analog output channels
-
Nominal signal range: 4–20 mA
-
Full signal range: 1–23 mA
-
Resolution: 12-bit
-
Accuracy: ±0.25% of span
Performance & Response
-
Response time: ≤25 ms (Railbus command to output)
-
Channel status reporting (active/inactive)
-
Configurable initialization state (predefined value)
-
Drive on fail-safe: predefined or last value
Diagnostics & Safety
-
Open-circuit detection per channel (0.7 ±0.25 mA)
-
Channel to Railbus isolation: 100 VAC
-
FM non-incendive parameters: 28.7 V, 33 mA, 0.17 μF, 11.0 mH
Electrical Requirements
-
Field power: 24 VDC bussed
-
Output compliance: 20 mA at 21.6 VDC (into 700 Ω load)
Environmental Ratings
-
Operating temperature: –40 °C to +70 °C
-
Storage temperature: –40 °C to +85 °C
-
Humidity: 5–95% non-condensing
-
Rugged industrial design for hazardous areas
FAQ
1. How many output channels does the 8104-AO-IP support?
It provides eight single-ended analog output channels for process control applications.
2. What is the nominal signal range of each output?
Each channel operates in the 4–20 mA range, with a full range of 1–23 mA.
3. Does the module include diagnostic features?
Yes, it offers per-channel open-circuit detection and channel status reporting.
4. What field power is required for operation?
The module requires 24 VDC bussed field power.
5. Can the module operate in hazardous environments?