Honeywell TC-OAV081 Experion Process I/O Analog Output Module

The Honeywell TC-OAV081 is an 8-channel isolated analog output module engineered for Honeywell DCS platforms, including Experion Process I/O systems. It provides high-precision signal output across eight independent channels, supporting both voltage and current configurations to interface with control valves, actuators, and variable-frequency drives in industrial automation networks.

Output Characteristics and Signal Protection

Each channel delivers configured outputs of -10.4 V to +10.4 V or 0 to 21 mA with a 25 ms update rate across all channels. Built-in electronic protection limits output currents to 21 mA or less during open or short circuits, while maintaining overvoltage protection up to 24 VAC/VDC at room temperature. High-voltage isolation tested at 2,550 VDC between user terminals and system logic prevents common-mode noise propagation across field wiring.

Hardware Specifications

Parameter Specification
Model TC-OAV081
Brand Honeywell
Product Type Analog Output Module
Number of Channels 8 isolated channels
Voltage Output Range -10.4 V to +10.4 V
Current Output Range 0 to 21 mA
Voltage Resolution 320 uV/count
Current Resolution 650 nA/count
Calibrated Accuracy Better than 0.05% of range at 25 deg C
Module Update Rate 25 ms for all channels
Output Settling Time Less than 2 ms to 95% of final value (resistive load)
Voltage Load Capability Greater than 2,000 ohm
Current Load Capability 0 to 750 ohm
Output Overvoltage Protection 24 VAC/VDC continuous at room temperature
Isolation Voltage 2,550 VDC for 1 second (user-to-system)
RFI Immunity Error less than 2% of range at 10 V/m (27 to 1,000 MHz)
Max Power Dissipation 6.9 W
Terminal Block TC-TBNH (20-position)
Dimensions 14.6 cm H x 14.0 cm D
Weight 0.2 kg

Frequently Asked Questions

Q: What output signal types and ranges does the TC-OAV081 support?

A: The module supports software-configurable voltage outputs from -10.4 V to +10.4 V and current outputs from 0 to 21 mA across its 8 channels.

Q: Which terminal block is required for field connections on the TC-OAV081?

A: Wiring connects via a 20-position TC-TBNH terminal block.

Q: How does the module respond to field short circuits or overvoltage conditions?

A: Output circuits are electronically current-limited to 21 mA or less under open or short circuits and withstand continuous overvoltage up to 24 VAC/VDC at room temperature.

You may also like