8 Channel Analog Output Module | IC200ALG326F GE VersaMax
8 Channel Analog Output Module | IC200ALG326F GE VersaMax
8 Channel Analog Output Module | IC200ALG326F GE VersaMax
/ 3

8 Channel Analog Output Module | IC200ALG326F GE VersaMax

  • Manufacturer: GE Fanuc

  • Part Number: IC200ALG326F

  • Condition:New with Original Package

  • Product Type: Analog Output Modules

  • Country of Origin: USA

  • Payment:T/T, Western Union

  • Shipping port: Xiamen

  • Warranty: 12 months

GE Fanuc IC200ALG326F VersaMax Analog Output Module

Configured for precision signal output in VersaMax control networks, the GE Fanuc IC200ALG320E (IC200ALG320 Analog Output Module) provides direct physical/electrical execution. This hardware component translates 13-bit digital output values from the controller into precise analog voltage or current signals for industrial process control.

Hardware Specifications

Parameter Specification
Model IC200ALG326F
Brand GE Fanuc / Emerson
Origin Refer to device label
Weight 0.20 kg (0.44 lbs)
Dimensions 120 mm x 90 mm x 40 mm
Operating Temp 0 deg C to +60 deg C
Power Consumption ~100 mA @ 5 VDC (backplane power)
Output Channels 8 single-ended current-sourcing outputs
Signal Range Jumper-selectable: 0–20 mA or 4–20 mA (also supports 0–10 VDC)
Resolution 13-bit DAC
Accuracy +/-0.3% of full scale
Update Rate < 1 ms per channel
Field Power Requirement 18–30 VDC (185 mA typical at full scale, 2 A max inrush)
Isolation Channel-to-channel and bus isolation

Backplane Bus Communication Velocity & Firmware Flash Integration

The module communicates across the VersaMax backplane bus using high-velocity data transfer to synchronize analog updates directly with CPU scan cycles. With firmware flash compatibility across the VersaMax series, the internal 13-bit D/A conversion engine processes output registers within < 1 ms per channel. Built-in diagnostic feedback continually verifies field loop continuity to prevent backplane bus stalling during loop faults.

Frequently Asked Questions

Q: Does this module support hot-swapping during active system operation?

A: The module supports hot-swap functionality when installed on a compatible VersaMax carrier, enabling replacement without interrupting backplane power or CPU execution.

Q: What external power configuration is required to drive the 8 analog current channels?

A: The module requires an external field power supply of 18–30 VDC. While internal logic draws approximately 100 mA from the 5 VDC backplane bus, the field power supply must handle 185 mA typical at full scale and account for a 2 A maximum inrush current.

Q: How are the output current ranges switched between 0–20 mA and 4–20 mA?

A: Range selection is jumper-selectable or software-configurable within the VersaMax controller rack hardware configuration settings.

Field Installation Guidelines

  • Mount the module onto standard 35 mm DIN rails or direct panel-mount baseplates using the VersaMax carrier locking mechanisms.
  • Route all 8 analog output wires using twisted, shielded pairs to eliminate high-frequency electromagnetic interference.
  • Connect signal cable shielding to a single-point protective earth (PE) ground terminal at the cabinet entrance to prevent ground loops.
  • Verify field power polarity and ensure the external supply delivers 18–30 VDC before enabling field sourcing loops.
You may also like