8-Channel Module ABB 3BSE020514R1 | AO801 Analog Output
Manufacturer: ABB
-
Part Number: AI820 3BSE008544R1
Condition:New with Original Package
Product Type: Distributed Control Systems
-
Country of Origin: Sweden
Payment:T/T, Western Union
Shipping port: Xiamen
Warranty: 12 months
Product Overview
The ABB AI820 (Part Number: 3BSE008544R1) functions as an 8-channel analog input module within the decentralized S800 I/O platform. This processing unit acquires precise analog voltage and current data from field-side sensors, process transmitters, and signal converters. Operating seamlessly with AC 800M controllers and the System 800xA automation architecture, the module translates physical field values into digital variables. We supply this product as a 100% brand new, original factory item from ABB Switzerland, ensuring accurate measurement loops and immediate synchronization with industrial process networks.
Technical Specifications
| Technical Parameter | Specification Data Value |
| Manufacturer | ABB |
| Model Designation | AI820 |
| Catalog Code | 3BSE008544R1 |
| Input Channels | 8 analog input channels |
| Current Signal Ranges | -20 to +20 mA, 0 to 20 mA, 4 to 20 mA |
| Voltage Signal Ranges | -10 to +10 V, 0 to 10 V, 2 to 10 V |
| Maximum Input Current | 30 mA under continuous circuit overload |
| Internal Input Resistance | Approximately 250 Ohm |
| Digital Resolution | 12-bit binary conversion |
| Isolation Design | Groupwise isolated from ground (RIV = 50 V) |
| Channel Conversion Time | Approximately 1 ms per channel |
| Maximum Power Dissipation | 1.7 W |
| Modulebus Power Draw (5V) | Approximately 80 mA |
| Modulebus Power Draw (24V) | 110 to 150 mA |
| Diagnostics Indicators | Front panel LEDs for Fault, Run, Warning |
| Maximum Thermal Drift | 100 ppm per degree Celsius |
| Ambient Operating Limits | 0 to +55 degrees Celsius |
| Storage Temperature Range | -40 to +70 degrees Celsius |
| Physical Module Size | 45 x 102 x 119 mm |
| Net Hardware Weight | 0.25 kg |
| Product Certifications | CE, UL, CSA, ATEX Zone 2, IECEx |
Engineering Advantages
-
Dual Voltage and Current Bipolar Signal Processing: Unlike standard unipolar modules, the AI820 accepts both voltage and current inputs across positive and negative ranges (such as -10 to +10 V and -20 to +20 mA). This versatile hardware configuration allows direct connection to specialized bipolar sensors and older legacy transmitters without requiring external signal conditioners.
-
Rapid Channel Scan Rates Optimize Monitoring Loops: A quick 1 ms conversion rate per channel ensures the module updates process values near-instantaneously. This high-speed sampling improves response times within fast-acting proportional-integral-derivative (PID) control loops on liquid pipelines and gas flow networks.
-
Groupwise Ground Isolation Suppresses Common Mode Noise: Groupwise electrical isolation with a Rated Isolation Voltage (RIV) of 50 V completely separates the external field-side cabling from the internal digital Modulebus backplane. This voltage barrier blocks common-mode noise, ground loops, and transient spikes from corrupting the central controller memory assets.
-
ATEX Zone 2 Compliance for Field-Level Integration: Official ATEX Zone 2 and IECEx certifications permit direct installation within volatile production environments. Control engineers can install the I/O rack closer to the field devices inside localized junction boxes, reducing expensive long-distance shielded cable runs.
FAQs
-
Is this specific AI820 module a 100% brand new product?
Yes. We sell this item exclusively as a 100% brand new, authentic component. It arrives inside original factory packaging from ABB with all original serial numbers and factory warranties intact.
-
Can I wire both a 4-20mA transmitter and a 0-10V sensor into the same module?
Yes. The AI820 accommodates multiple voltage and current ranges. However, because the module utilizes groupwise isolation rather than channel-to-channel isolation, you must ensure that all connected loops share a compatible reference potential to prevent cross-channel interference.
-
What happens if a field transmitter fails and drives excessive current into an input?
The input channels feature robust electrical protection that withstands continuous overload currents up to 30 mA. This protection profile isolates current surges and prevents thermal damage from cascading into the internal module electronics.
-
Which accessory is required to mount this module onto a control panel rail?
The AI820 requires a matching ABB S800 Module Termination Unit (MTU), such as a compact or extended terminal unit base. The MTU secures the module onto the standard DIN-rail and provides the physical screw or spring terminals for the 8 field circuit lines.