Product Overview
The 8125-DI-DC is a high-density digital input module from GE’s PAC8000 series, designed for industrial I/O applications. It provides 32 discrete input channels, ideal for monitoring switches, proximity detectors, and other digital field devices. The module draws power directly from the PAC8000 backplane, simplifying installation while maintaining robust performance.
Built-in line fault detection and selectable response times ensure accurate diagnostics and reliable operation in harsh environments. Pulse counting and latching features allow advanced monitoring of fast digital signals, making the 8125-DI-DC suitable for demanding process control systems.
Functional Description
The 8125-DI-DC module provides source-type digital inputs compatible with dry contact switches and proximity detectors. It features high-speed input sampling (8 kHz) and advanced fault detection, including open and short-circuit monitoring. Channel-to-railbus isolation enhances safety and signal integrity. Designed for DIN rail mounting, this module integrates seamlessly into PAC8000 modular I/O systems.
Technical Specifications
| Parameter | Details |
|---|---|
| Model Number | 8125-DI-DC |
| Manufacturer | GE (Emerson PAC8000 series) |
| Product Type | Digital Input Module |
| Number of Channels | 32 digital inputs |
| Input Type | Source type (dry contact/proximity detector) |
| Input Voltage Range | 18–30 VDC |
| On/Off Current Threshold | ON > 2.1 mA, OFF < 1.2 mA |
| Response Time | Selectable: 2–512 ms |
| System Current Consumption | 50 mA |
| Field Current Consumption | 190 mA |
| Short Circuit Current | 8.6 mA typical |
| Output Resistance | 950 Ω typical |
| Open Circuit Output Voltage | 8.2 VDC typical |
| Line Fault Detection | Short circuit <100 Ω, Open circuit <50 μA |
| Pulse Counting Frequency | Up to 500 Hz |
| Minimum Pulse Width | 250 μs |
| Input Sampling Rate | 8 kHz (all 32 channels) |
| Isolation | Channel to Railbus: 250 VAC |
| Standards | NAMUR, DIN 19234 |
| Operating Temperature | –40 °C to +70 °C |
| Storage Temperature | –40 °C to +85 °C |
| Mounting | DIN rail (flat, T-type, G-type) |
| Certifications | CE, UL, CSA compliant |