{"product_id":"8201-hi-is-ge-mark-vi-dcs-analog-input-cards","title":"8201-HI-IS GE Mark VI DCS Analog Input Cards","description":"\u003ch2\u003eGE 8201-HI-IS Analog Input Module\u003c\/h2\u003e\n\u003cp\u003eConfigured for high-precision signal acquisition in distributed control system platforms, the \u003cstrong\u003eGE 8201-HI-IS\u003c\/strong\u003e (\u003cstrong\u003e8201-HI-IS\u003c\/strong\u003e Analog Input Module) provides direct physical\/electrical execution. The hardware component processes 8 single-ended field-side analog channels across a nominal 4-20 mA range (0.5 to 22 mA full scale) for 2-wire transmitters, executing onboard signal conditioning, HART pass-through communications, and 16-bit analog-to-digital conversion. Featuring intrinsically safe (Ex i) field circuits with integrated transmitter power, line fault detection, and 60 VAC channel-to-railbus galvanic isolation, the unit digitizes process variables and transmits real-time status data directly across the system bus.\u003c\/p\u003e\n\u003ch3\u003eSuffix Breakdown \u0026amp; Model Matrix\u003c\/h3\u003e\n\u003cp\u003eThe model number \u003cstrong\u003e8201-HI-IS\u003c\/strong\u003e follows a functional suffix breakdown designating module performance and physical safety parameters:\u003c\/p\u003e\n\u003cul\u003e\n\u003cli\u003e\n\u003cstrong\u003e8201\u003c\/strong\u003e: Identifies the base I\/O module platform hardware architecture.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eHI\u003c\/strong\u003e: Designates High-density Intrinsically safe \/ HART-enabled analog input functionality.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eIS\u003c\/strong\u003e: Confirms built-in Intrinsic Safety barrier protection for Hazardous field circuit interfaces.\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003ch3\u003eHardware Specifications\u003c\/h3\u003e\n\u003cfigure class=\"table\"\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr\u003e\n\u003cth\u003e\u003cstrong\u003eParameter\u003c\/strong\u003e\u003c\/th\u003e\n\u003cth\u003e\u003cstrong\u003eSpecification\u003c\/strong\u003e\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003eModel\u003c\/td\u003e\n\u003ctd\u003e8201-HI-IS\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eBrand\u003c\/td\u003e\n\u003ctd\u003eGE\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOrigin\u003c\/td\u003e\n\u003ctd\u003eUSA\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eWeight\u003c\/td\u003e\n\u003ctd\u003e0.26 kg (260 g)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eDimensions\u003c\/td\u003e\n\u003ctd\u003e2.2 cm x 12.4 cm x 12.6 cm (42 mm Module Width)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOperating Temp\u003c\/td\u003e\n\u003ctd\u003e-20 deg C to +60 deg C\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003ePower Consumption\u003c\/td\u003e\n\u003ctd\u003e2.5 W Nominal\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eChannel Capacity\u003c\/td\u003e\n\u003ctd\u003e8 Single-Ended Input Channels\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eSignal Range\u003c\/td\u003e\n\u003ctd\u003e4 to 20 mA Nominal (0.5 to 22 mA Full Range)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eA\/D Resolution\u003c\/td\u003e\n\u003ctd\u003e16-bit\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eField Power Supply\u003c\/td\u003e\n\u003ctd\u003eIn-built Supply (15 V Min. Voltage to Transmitter @ 20 mA)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eLine Fault Detection\u003c\/td\u003e\n\u003ctd\u003eShort Circuit \u0026gt; 21.5 mA, Open Circuit \u0026lt; 0.5 mA\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eGalvanic Isolation\u003c\/td\u003e\n\u003ctd\u003eAny Channel to Railbus - 60 VAC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003c\/figure\u003e\n\u003ch3\u003eBackplane Bus Communication Velocity and Firmware Flash Compatibility\u003c\/h3\u003e\n\u003cp\u003eThe \u003cstrong\u003eGE 8201-HI-IS\u003c\/strong\u003e transfers digitized process variables and HART status reports directly across the high-speed railbus interface to synchronize data execution with central control units. Rapid bus communication velocity prevents scan cycle latencies during continuous high-density I\/O sampling. Firmware flash memory compatibility ensures smooth handshaking protocols between the module micro-controller and central system software suites, allowing online parameter configuration and stable data path execution without interrupting active backplane cycles.\u003c\/p\u003e\n\u003ch3\u003eFrequently Asked Questions\u003c\/h3\u003e\n\u003cp\u003eQ: How does the module handle line fault detection on active field circuits?\u003c\/p\u003e\n\u003cp\u003eA: Onboard detection circuitry continuously monitors loop currents, triggering a line fault status flag when circuit current drops below 0.5 mA (open circuit) or rises above 21.5 mA (short circuit).\u003c\/p\u003e\n\u003cp\u003eQ: Does the 8201-HI-IS require external power supplies for connected field transmitters?\u003c\/p\u003e\n\u003cp\u003eA: No, the module incorporates an internal power supply capable of delivering a minimum of 15 V to 2-wire field transmitters at 20 mA loop operating levels.\u003c\/p\u003e\n\u003cp\u003eQ: Are individual channels isolated from one another within the same module?\u003c\/p\u003e\n\u003cp\u003eA: Individual channels share a common return and lack channel-to-channel isolation, but all channels maintain 60 VAC galvanic isolation relative to the railbus backplane.\u003c\/p\u003e\n\u003ch3\u003eField Installation Guidelines\u003c\/h3\u003e\n\u003cp\u003eFollow these core physical assembly and wiring steps during system field setup:\u003c\/p\u003e\n\u003col\u003e\n\u003cli\u003e\n\u003cstrong\u003eDIN-Rail Mounting\u003c\/strong\u003e: Align the module key code A1 with the baseboard slot and push the module firmly onto the railbus carrier until retaining clips engage.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eField Terminal Wiring\u003c\/strong\u003e: Connect 2-wire transmitter leads to designated terminal block points, verifying stripped conductor ends seat securely inside terminal clamps.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eShield Earthing\u003c\/strong\u003e: Terminate field cable drain shields at the main cabinet ground bus, establishing a single-point earth return to eliminate high-frequency noise coupling.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eHART Configuration\u003c\/strong\u003e: Enable HART pass-through communication via system software to allow field device parameterization without attaching external handheld communicators.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003ePower-On Inspection\u003c\/strong\u003e: Verify railbus power rail voltages before energizing the system, observing module channel status LEDs to confirm normal initialization.\u003c\/li\u003e\n\u003c\/ol\u003e","brand":"GE Fanuc","offers":[{"title":"Default Title","offer_id":44451821486179,"sku":"8201-HI-IS","price":120.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0583\/5246\/8067\/files\/460._b48be87b-a946-4878-9691-20e00b52c46f.jpg?v=1786010385","url":"https:\/\/www.autocontrolglobal.com\/products\/8201-hi-is-ge-mark-vi-dcs-analog-input-cards","provider":"AutoControl Global","version":"1.0","type":"link"}