AAI141-S00/K4A00 Yokogawa CENTUM VP Analog Input Module
AAI141-S00/K4A00 Yokogawa CENTUM VP Analog Input Module
AAI141-S00/K4A00 Yokogawa CENTUM VP Analog Input Module
/ 3

AAI141-S00/K4A00 Yokogawa CENTUM VP Analog Input Module

  • Manufacturer: Yokogawa

  • Part Number: AAI141-S00/K4A00

  • Condition:New with Original Package

  • Product Type: Analog Input Modules

  • Country of Origin: Japan

  • Payment:T/T, Western Union

  • Shipping port: Xiamen

  • Warranty: 12 months

 

Yokogawa AAI141-S00/K4A00 Analog Input Module

The Yokogawa AAI141-S00/K4A00, also cataloged as the AAI141 Analog Input Module, operates as a dedicated hardware component for 16-channel non-isolated 4-20 mA DC signal acquisition within Yokogawa CENTUM VP and FIO networks.

Suffix Breakdown & Model Matrix

Code Type Description
AAI141 Base Model Analog Input Module (4 to 20 mA, 16-channel, Non-Isolated)
-S Type Code Standard Type
0 Hardware Option Basic Type (No explosion protection)
0 Environmental Option Basic Type
/K4A00 Option Code With KS Cable Interface Adapter (Model: ATK4A-00)

Hardware Specifications

Parameter Specification
Model AAI141-S00/K4A00
Brand Yokogawa
Origin Standard Manufacturer Sourcing
Weight 0.2 kg
Dimensions Standard Yokogawa FIO Module Dimensions
Operating Temp 0 to 60 deg C
Power Consumption 310 mA at 5 VDC, 450 mA at 24 VDC
Input Channels 16 channels, non-isolated
Input Signal 4 to 20 mA DC
Allowable Input Current 27 mA max.
Input Resistance 400 ohm at 20 mA to 1 kohm at 4 mA
Input Resistance (Power OFF) 500 kohm or greater
Measurement Accuracy +/-16 uA
Data Update Period 10 ms
Step Response Time Approx. 100 ms
Temperature Drift +/-16 uA per 10 deg C
Transmitter Power Supply >= 14.8 VDC at 20 mA, <= 26.4 VDC at 0 mA
Interface Adapter ATK4A-00 KS Cable Interface Adapter

Process Control & DCS Instrumentation

The module provides high-density signal acquisition for common-ground 4-20 mA loops, processing 16 analog channels into digital process values across a 10 ms update window. Internal power distribution circuits supply integrated loop power to 2-wire field transmitters with a guaranteed minimum terminal voltage of 14.8 VDC at 20 mA. Active current-limiting circuitry caps input overload conditions at 27 mA, while an unpowered input impedance exceeding 500 kohm maintains circuit integrity during node maintenance.

Frequently Asked Questions

Q: How does the non-isolated channel architecture affect loop wiring design on site?

A: All 16 channels share a common internal signal ground. Consequently, connected 2-wire transmitters or external loop power sources must operate on a unified reference potential to avoid cross-channel ground loops.

Q: What role does the /K4A00 option code play in field connectivity?

A: The /K4A00 option mounts an ATK4A-00 adapter onto the front interface of the module. This allows a standard pre-fabricated multi-core KS cable to plug directly into the module and route signals to external terminal units, such as the AEA4D, eliminating point-to-point discrete cabinet wiring.

Field Installation Guidelines

Align the module with the card guide rails of the designated FIO node chassis slot and slide it inward until the backplane bus header seats fully. Tighten the top and bottom panel retention screws to secure the physical assembly and verify cabinet frame grounding continuity.

Connect the KS multi-core interface cable securely to the front ATK4A-00 adapter using the integrated latching fasteners. Route signal lines through low-voltage ducting, maintaining a minimum clearance of 200 mm from three-phase AC cabling. Connect incoming cable shields to the cabinet ground bar at a single point to prevent high-frequency noise from corrupting measurement accuracy.

You may also like