AAI841-S00 S2 Yokogawa 1-5V Input 4-20mA Output Board
AAI841-S00 S2 Yokogawa 1-5V Input 4-20mA Output Board
AAI841-S00 S2 Yokogawa 1-5V Input 4-20mA Output Board
/ 3

AAI841-S00 S2 Yokogawa 1-5V Input 4-20mA Output Board

  • Manufacturer: Yokogawa

  • Part Number: AAI841-S00 S2

  • Condition:New with Original Package

  • Product Type: CENTUM VP DCS Components

  • Country of Origin: Japan

  • Payment:T/T, Western Union

  • Shipping port: Xiamen

  • Warranty: 12 months

Product Overview

The Yokogawa AAI841-S00 S2 performs dual-function data management tasks within CENTUM VP distributed control systems (DCS). This high-density analog input/output module combines data collection and field actuation mechanisms into a single slot footprint. The card simultaneously monitors 8 non-isolated analog input channels and drives 8 non-isolated analog output channels. Process plants utilize this mixed I/O architecture to manage proportional valves, variable speed drives, and process transmitters from a centralized point, maximizing rack utilization in non-isolated loop environments.

Part Number Breakdown

Yokogawa builds field modules using structured codes to denote specific feature sets. The AAI841 configuration uses the following matrix:

  • AAI841: Base model for analog input and analog output module (8-channel inputs, 8-channel outputs)

  • -S: Standard type module architecture

  • 0: Always 0 (Standard placeholder)

  • 0: Basic type non-isolated parameter set

  • S2: Generation 2 hardware enhancement version

Technical Specifications

This 100% brand new, original Yokogawa hardware arrives in original factory packaging. All technical metrics comply with standard ASCII formatting.

  • Model: AAI841-S00 S2

  • Module Type: Analog Input / Output Mixed Module

  • System Platform Natively Supported: Yokogawa CENTUM VP DCS

  • Analog Input Channel Count: 8 channels (shared common ground, non-isolated)

  • Analog Output Channel Count: 8 channels (shared common ground, non-isolated)

  • Input Signal Voltage Range: 1 to 5 V DC (or 4 to 20 mA via external shunt resistor)

  • Output Signal Current Range: 4 to 20 mA DC

  • Internal Data Update Period: 10 ms

  • Input Step Response Interval: 100 ms

  • Output Step Response Interval: 40 ms

  • Physical Module Weight: 1.0 Kg

  • Country of Origin: Japan

Engineering Advantages

  • Cuts Terminal Cabinet Space Requirements in Half: Standard DCS configurations separate input and output channels onto individual dedicated cards, doubling the required rack hardware. The AAI841-S00 S2 integrates an 8-channel input array and an 8-channel output array into one module casing. This consolidated configuration saves significant backplane space, allowing engineers to build smaller marshalling cabinets and reduce overall footprint costs.

  • Accelerates Installation via Flexible Interface Couplings: Fixed terminal designs complicate field maintenance and slow down initial commissioning activities. This card supports three independent wiring styles: direct terminal block connection, KS cable interface adapters, or high-density MIL ribbon cables. Installers pick the preferred termination method to match existing plant wiring patterns, shortening field labor hours.

  • Delivers Swift Control Loop Updates: Dynamic chemical reactions, gas blending skids, and laboratory testing loops require fast signal updates to prevent process deviation. The AAI841-S00 S2 processes data updates every 10 ms, driving the analog outputs to full step execution within 40 ms. This fast response profile guarantees tight, predictable tracking across highly volatile process variables.

  • Simplifies Common-Ground Sensor Loop Architectures: In self-contained systems like laboratory instrumentation skids or environmental monitoring packages, common-ground loops do not face ground-potential shifts. The non-isolated channel architecture on this module eliminates unnecessary isolation electronics. This lean design provides a highly cost-effective, straightforward connection choice for plants that use uniform, noise-free local power distribution.

FAQs

  • Q: Is this AAI841-S00 S2 module brand new and genuine?A: Yes. We offer this item as a 100% brand new, original, and genuine factory product from Yokogawa Japan. The module arrives in its unopened, original manufacturer packaging complete with factory inspection stamps.

  • Q: Can this non-isolated module tolerate heavy electrical noise between separate field instruments?A: No. Because the input and output channels share a common internal ground line, you should only deploy this module in environments where field devices share the same ground potential or reside within a shielded local system enclosure. If your application involves long field cable runs exposed to high ground-loop currents or heavy industrial noise, you must use an isolated model variant or place external signal isolators between the field devices and the module terminals.

  • Q: How does the module receive standard 4 to 20 mA input signals if the specification lists 1 to 5 V?A: The input channels read voltage drops across a 1 to 5 V range natively. To connect standard 4 to 20 mA field transmitters, you mount a high-precision 250 Ohm shunt resistor across the target input terminal points. The current passing through the resistor generates the corresponding 1 to 5 V drop for the module to read.

You may also like