ABB DOS810 3BSE078768R1 Digital Output Module
/ 1

ABB DOS810 3BSE078768R1 Digital Output Module

  • Manufacturer: ABB

  • Part Number: DOS810 3BSE078768R1

  • Condition:New with Original Package

  • Product Type: Digital Output Module

  • Country of Origin: Sweden

  • Payment:T/T, Western Union

  • Shipping port: Xiamen

  • Warranty: 12 months

The DOS810 is a Digital Output (24V / 0.6A) Signal Conditioning Module supporting 2-wire devices.

Features and Benefits

  • Digital output for 2-wire field devices
  • 24 V / 0.6 A current sourcing
  • Can be used in hazardous areas
  • Field power sourced from the power injection
  • Short circuit proof, electronically current limited to 0.6 A
  • Built-in inductive load suppression, free-wheeling diode
  • Galvanic isolation
  • Protected against wrong wiring

Diagnostics

  • Loop supervision (open circuit and short circuit)
  • Hardware error supervision
  • Communication supervision
  • Internal power supervision
  • Power injection supervision
  • OSP (Output Set to Predetermined value)
  • Single loop granularity - each SCM handles a single channel
  • Supports hot swap
  • Mechanical locking slider which turns off field device power and/or output before removal
  • Field disconnect function which can galvanically separate the field loop wiring from the SCM during commissioning and maintenance
  • All SCMs have electronic current limitation
  • Mechanical keying to prevent insertion of wrong module type after commissioning

General Info

  • Article number: 3BSE078768R1
  • Type: Digital Output Module
  • Number of channels: 1
  • Signal specification: 24 V DC / 0.6 A
  • HART: N/A
  • SOE: N/A
  • Redundancy: Yes
  • Hot swap: Yes
  • High integrity: No
  • Intrinsic safety: No
  • Mechanics: Select I/O

Detailed Data

  • Supported field devices: 2-wire
  • Isolation: Galvanic isolation to system. Routine tested at factory with 3060 VDC.
  • Field power: Current limited
  • Diagnostics: Loop supervision (short circuit and open circuit), Internal hardware supervision, Communication supervision, Internal power supervision, Power injection supervision
  • Calibration: Factory calibration
  • Power dissipation: 0.36 W
  • Installation in Hazardous Area/Locations: Yes/Yes
  • IS barrier: No
  • Output load. Max inductor time constant (L/R): 40 - 5000 Ω, 50 ms
  • Field Input Robustness: ±35 V between all terminals
  • Input voltage range: 19.2 ... 30 V

Environment and Certification

  • Temperature, Operating: -40 °C (-40 °F) to +70 °C (158 °F)
  • Temperature, Storage: -40 °C (-40 °F) to +85 °C (185 °F)
  • Pollution degree: Pollution Degree 2 acc. to IEC 60664-1
  • Relative humidity: 5 to 95 %, non-condensing
  • Altitude: -1000 to 5000 m (restrictions apply)
  • Mechanical operating conditions: IEC 61131-2
  • EMC: IEC/EN 61000-6-4, IEC/EN 61000-6-2
  • Overvoltage categories: Category II acc. to IEC 60664-1
  • Protection class: IP20 acc. to IEC 60529
  • CE-marking: Yes
  • UKCA: Yes
  • Electrical Safety: IEC/EN 61010-1, UL 61010-1, CSA-C22.2 No. 61010-1-12, IEC/EN 61010-2-201, UL 61010-2-201, CSA C22.2 No. 61010-2-201
  • Marine certification: DNV, ABS
  • Corrosive atmosphere: G3
  • RoHS compliance: EU RoHS, UAE RoHS, CN RoHS
  • WEEE compliance: EU

Hazardous Area Certifications

  • ATEX: II 3G Ex nA IIC T4 Gc, II 3G Ex ec IIC T4 Gc, II 3G Ex ic nA IIC T4 Gc, II 3G Ex ic ec IIC T4 Gc
  • IECEx: Available on IPA: II 3G Ex nA IIC T4 Gc, II 3G Ex ec IIC T4 Gc, II 3G Ex ic nA IIC T4 Gc, II 3G Ex ic ec IIC T4 Gc
  • US/CAN: cULus CL I, ZN 2, AEx ec IIC T4 Gc, Ex ec IIC T4 Gc X, CL I, ZN 2, AEx nA IIC T4 Gc, Ex nA IIC T4 Gc X, CL I, DIV 2, Groups A-D T4
  • CCC: Ex ec IIC T4 Gc, Ex ec ic IIC T4 Gc

Dimensions

  • Width: 77.9 mm
  • Depth: 105 mm
  • Height: 9.8 mm
  • Weight (including base): 73 g