ABB NTAI02 Bailey INFI 90 Thermocouple Termination Board
Manufacturer: ABB
-
Part Number: NTAI02
Condition:New with Original Package
Product Type: Termination Units
-
Country of Origin: Sweden
Payment:T/T, Western Union
Shipping port: Xiamen
Warranty: 12 months
ABB NTAI02 Bailey INFI 90 Analog Input Termination Unit
The ABB Bailey NTAI02 is a 16-channel analog input termination unit designed for the Bailey INFI 90 Distributed Control System (DCS). It marshals thermocouple and millivolt signals directly from field sensors and routes them to IMASM02 Thermocouple Slave Modules, which subsequently interface with IMAMM03 Analog Master Modules for processing.
Architecture and Module Pairing
Each NTAI02 unit provides connection points for up to 16 analog input channels. To scale input density within a system cabinet, up to four NTAI02 termination units can be connected to a single IMASM02 slave module. This modular topology streamlines cabinet cable management and simplifies point-to-point field wiring for high-density temperature and millivolt monitoring.
Mechanical and Custom Regulatory Data
Designed for panel or rack mounting inside industrial control enclosures, the termination unit measures 7.62 cm x 35.6 cm x 25.4 cm (3.0 in x 14.0 in x 10.0 in) and weighs 0.5 kg. It is classified under HS Code 85389081, with manufacturing locations including Sweden, Malta, or India depending on supply batch.
Technical Parameters
| Parameter | Specification |
|---|---|
| Model | NTAI02 |
| Brand | ABB Bailey |
| Product Type | Analog Input Termination Unit |
| System Compatibility | ABB Bailey INFI 90 DCS |
| Supported Signal Types | Thermocouple, millivolt (mV) inputs |
| Channel Capacity | 16 input channels per unit |
| Interfacing Modules | IMASM02 Thermocouple Slave Module, IMAMM03 Analog Master Module |
| Expansion Capacity | Up to 4 NTAI02 units per IMASM02 slave module |
| Dimensions (L x W x H) | 7.62 cm x 35.6 cm x 25.4 cm |
| Weight | 0.5 kg |
| HS Code | 85389081 |
| Country of Origin | Sweden, Malta, or India (depending on supply batch) |
Frequently Asked Questions
Q: What signal types does the ABB Bailey NTAI02 termination unit accept? A: The unit accepts thermocouple and millivolt (mV) analog input signals from field transmitters and sensors.
Q: How many NTAI02 units can connect to a single IMASM02 slave module? A: Up to four NTAI02 termination units can be connected to one IMASM02 Thermocouple Slave Module, expanding capacity up to 64 channels per slave interface.