ABB UR600IR/BGT Uvisor Infrared Flame Scanner Detector
Manufacturer: ABB
-
Part Number: UR600IR/BGT
Condition:New with Original Package
Product Type: Flame Detectors
-
Country of Origin: Sweden
Payment:T/T, Western Union
Shipping port: Xiamen
Warranty: 12 months
ABB UR600IR/BGT Uvisor Infrared Flame Scanner
The ABB UR600IR/BGT, also cataloged as the UR600IR/BGT Infrared Flame Scanner, operates as a dedicated hardware component for combustion flame flicker monitoring within ABB Uvisor platforms.
Hardware Specifications
| Parameter | Specification |
|---|---|
| Model | UR600IR/BGT |
| Brand | ABB |
| Origin | USA |
| Weight | 1.0 kg |
| Dimensions | 94 mm x 94 mm x 172 mm |
| Operating Temp | -10 deg C to +85 deg C (Max 350 deg C with fiber extension) |
| Power Consumption | ~300 mW DC (Supplied through Uvisor MFD) |
| Sensor Element | Lead Sulfide (PbS) Infrared Photodetector |
| Spectral Range | 600 nm to 3000 nm |
| Protection Class | IP66 / NEMA 4X |
| Hazardous Certification | EEx-d IIC T6 (ATEX Certified) |
| Air Purge Requirement | 115 l/min (4 SCFM) |
Backplane Bus Communication Velocity & Deterministic Network Execution
The ABB UR600IR/BGT processes optical flicker frequencies across the 600 nm to 3000 nm spectral band, converting raw infrared photon excitation into analog pulse trains. The unit routes output signals to the Uvisor MFD central processing subrack, where hardware logic executes real-time amplitude and frequency analysis without backplane bus latency. Continuous internal self-checking routines verify sensor element integrity during active scan intervals, asserting discrete fault flags to the main burner management backplane if optical path degradation or circuit drift occurs.
Frequently Asked Questions
Q: How does the ABB UR600IR/BGT scanner interface with the control processing system?
A: The scanner connects directly to the ABB Uvisor MFD control unit, drawing ~300 mW DC operational power through the signal cable while transmitting analog flicker frequencies for central evaluation.
Q: What mechanism protects the scanner optics from ambient thermal stress in high-temperature combustion zones?
A: Deployments in environments exceeding the baseline -10 deg C to +85 deg C operating limit utilize a fiber-optic extension capable of withstanding continuous temperatures up to 350 deg C, supplemented by a 115 l/min air purge system.
Q: Is the ABB UR600IR/BGT suitable for installation in classified explosion-proof areas?
A: Yes, the heavy-duty enclosure holds ATEX and EEx-d IIC T6 approvals and carries an IP66 / NEMA 4X ingress protection rating for hazardous locations.
Field Installation Guidelines
Verify that burner fuel supply valves are locked closed and primary loop power from the Uvisor MFD interface is isolated before installing or servicing the ABB UR600IR/BGT scanner assembly.
First, secure the IP66/NEMA 4X aluminum housing onto the sight pipe mounting flange. Connect an active instrument air line delivering at least 115 l/min (4 SCFM) to the air purge port to prevent soot accumulation on the front optical lens assembly.
Second, terminate the shielded signal cable according to ABB Uvisor field wiring diagrams. Ensure the cable drain wire bonds directly to the panel grounding bus bar at a single point to mitigate electromagnetic noise caused by nearby high-voltage ignition transformers.