ABL8RPS24100 Phaseo 240W Power Supply | Schneider
Manufacturer: Schneider
-
Part Number: ABL8RPS24100
Condition:New with Original Package
Product Type: Modicon Switching Power Supplies
-
Country of Origin: France
Payment:T/T, Western Union
Shipping port: Xiamen
Warranty: 12 months
Schneider Electric ABL8RPS24100 Phaseo Power Supply
The Schneider Electric ABL8RPS24100 is a 240 W regulated switch-mode power supply in the Phaseo series, delivering 24 VDC at 10 A for PLC, sensor, relay, and actuator circuits. It accepts single-phase AC (100-120 VAC or 100-240 VAC per source), phase-to-phase AC (200-500 VAC), and 110-220 VDC inputs. Key features include 24-28.8 VDC output adjustment, a 1.5 x In (15 A) 4-second boost, an integrated PFC / anti-harmonic filter, and parallel or series output coupling.
Input, Output, and Protection Characteristics
Wide-range AC input operation at 47-63 Hz supports direct connection to single-phase mains or 400/480 VAC phase-to-phase supplies without step-down transformers. An integrated low-frequency anti-harmonic / PFC filter limits line harmonics, with inrush current of 30-35 A and 31 W power dissipation.
On the load side, output voltage adjusts from 24 to 28.8 VDC to compensate for cable voltage drop, while a 150% (15 A) boost for 4 s handles transient inrush loads. Electronic protection covers overload and short-circuit (manual or automatic reset), thermal fault (automatic reset), overvoltage (30-32 VDC, manual reset), and undervoltage shutdown (below 21.6 VDC).
Mechanical and Operating Conditions
Housed in an IP20 enclosure measuring 125 x 86 x 145 mm (H x W x D) and weighing 1.0 kg, the unit mounts on a 35 mm DIN rail or panel. LED indicators provide local status monitoring, and outputs support parallel or series coupling. Full-load operation runs from -20 to +45 deg C, with derating up to +60 deg C.
Technical Specifications
| Parameter | Specification |
|---|---|
| Model | ABL8RPS24100 |
| Brand | Schneider Electric |
| Product Series | Phaseo / Modicon Power Supply |
| Product Type | Regulated Switch-Mode Power Supply |
| Nominal Input Voltage | 100-120 VAC (single-phase) / 100-240 VAC (first source), 200-500 VAC (phase-to-phase), 110-220 VDC |
| Input Voltage Limits | 85-132 VAC / 170-550 VAC (85-264 VAC, 100-250 VDC in first source) |
| Input Frequency | 47-63 Hz |
| Inrush Current | 30-35 A |
| Power Factor | 0.68 at 240 VAC / 0.69 at 120 VAC (0.65 in first source) |
| Harmonic Filtering | Integrated anti-harmonic / PFC filter (low-frequency harmonics) |
| Efficiency | 85% - 87% |
| Power Dissipation | 31 W |
| Nominal Output Voltage | 24 VDC |
| Adjustable Output Voltage | 24-28.8 VDC |
| Rated Output Current | 10 A |
| Temporary Current Boost | 1.5 x In / 150% (15 A) for 4 s |
| Rated Power | 240 W |
| Output Coupling | Parallel or series |
| Overload Protection | Manual or automatic reset |
| Short-Circuit Protection | Manual or automatic reset |
| Overvoltage Protection | 30-32 VDC, manual reset |
| Undervoltage Protection | Shutdown below 21.6 VDC |
| Thermal Protection | Automatic reset |
| Status Indicators | LED indicators |
| Mounting | 35 mm DIN rail or panel |
| Ingress Protection | IP20 |
| Operating Temperature | -20 to +45 deg C (no derating), up to +60 deg C with derating |
| Storage Temperature | -40 to +85 deg C |
| Dimensions (H x W x D) | 125 x 86 x 145 mm |
| Net Weight | 1.0 kg |
| Marking | CE |
Frequently Asked Questions
Q: Can the ABL8RPS24100 operate on both single-phase and phase-to-phase AC supplies? A: Yes, it accepts single-phase AC (100-120 VAC / 100-240 VAC per source) as well as 200-500 VAC phase-to-phase AC and 110-220 VDC inputs at 47-63 Hz.
Q: Does the ABL8RPS24100 support parallel or series output connection? A: Yes, the output stage supports both parallel and series coupling configurations, alongside a 24-28.8 VDC adjustment range.
Q: How do the protection functions reset after a fault on the ABL8RPS24100? A: Overload and short-circuit protections support manual or automatic reset, thermal protection resets automatically, overvoltage protection (30-32 VDC) requires manual reset, and undervoltage shuts down below 21.6 VDC.