Schneider Electric ABL8RPS24100 Phaseo Power Supply

The Schneider Electric ABL8RPS24100 is a 240 W regulated switch-mode power supply in the Phaseo series, delivering 24 VDC at 10 A for PLC, sensor, relay, and actuator circuits. It accepts single-phase AC (100-120 VAC or 100-240 VAC per source), phase-to-phase AC (200-500 VAC), and 110-220 VDC inputs. Key features include 24-28.8 VDC output adjustment, a 1.5 x In (15 A) 4-second boost, an integrated PFC / anti-harmonic filter, and parallel or series output coupling.

Input, Output, and Protection Characteristics

Wide-range AC input operation at 47-63 Hz supports direct connection to single-phase mains or 400/480 VAC phase-to-phase supplies without step-down transformers. An integrated low-frequency anti-harmonic / PFC filter limits line harmonics, with inrush current of 30-35 A and 31 W power dissipation.

On the load side, output voltage adjusts from 24 to 28.8 VDC to compensate for cable voltage drop, while a 150% (15 A) boost for 4 s handles transient inrush loads. Electronic protection covers overload and short-circuit (manual or automatic reset), thermal fault (automatic reset), overvoltage (30-32 VDC, manual reset), and undervoltage shutdown (below 21.6 VDC).

Mechanical and Operating Conditions

Housed in an IP20 enclosure measuring 125 x 86 x 145 mm (H x W x D) and weighing 1.0 kg, the unit mounts on a 35 mm DIN rail or panel. LED indicators provide local status monitoring, and outputs support parallel or series coupling. Full-load operation runs from -20 to +45 deg C, with derating up to +60 deg C.

Technical Specifications

Parameter Specification
Model ABL8RPS24100
Brand Schneider Electric
Product Series Phaseo / Modicon Power Supply
Product Type Regulated Switch-Mode Power Supply
Nominal Input Voltage 100-120 VAC (single-phase) / 100-240 VAC (first source), 200-500 VAC (phase-to-phase), 110-220 VDC
Input Voltage Limits 85-132 VAC / 170-550 VAC (85-264 VAC, 100-250 VDC in first source)
Input Frequency 47-63 Hz
Inrush Current 30-35 A
Power Factor 0.68 at 240 VAC / 0.69 at 120 VAC (0.65 in first source)
Harmonic Filtering Integrated anti-harmonic / PFC filter (low-frequency harmonics)
Efficiency 85% - 87%
Power Dissipation 31 W
Nominal Output Voltage 24 VDC
Adjustable Output Voltage 24-28.8 VDC
Rated Output Current 10 A
Temporary Current Boost 1.5 x In / 150% (15 A) for 4 s
Rated Power 240 W
Output Coupling Parallel or series
Overload Protection Manual or automatic reset
Short-Circuit Protection Manual or automatic reset
Overvoltage Protection 30-32 VDC, manual reset
Undervoltage Protection Shutdown below 21.6 VDC
Thermal Protection Automatic reset
Status Indicators LED indicators
Mounting 35 mm DIN rail or panel
Ingress Protection IP20
Operating Temperature -20 to +45 deg C (no derating), up to +60 deg C with derating
Storage Temperature -40 to +85 deg C
Dimensions (H x W x D) 125 x 86 x 145 mm
Net Weight 1.0 kg
Marking CE

Frequently Asked Questions

Q: Can the ABL8RPS24100 operate on both single-phase and phase-to-phase AC supplies? A: Yes, it accepts single-phase AC (100-120 VAC / 100-240 VAC per source) as well as 200-500 VAC phase-to-phase AC and 110-220 VDC inputs at 47-63 Hz.

Q: Does the ABL8RPS24100 support parallel or series output connection? A: Yes, the output stage supports both parallel and series coupling configurations, alongside a 24-28.8 VDC adjustment range.

Q: How do the protection functions reset after a fault on the ABL8RPS24100? A: Overload and short-circuit protections support manual or automatic reset, thermal protection resets automatically, overvoltage protection (30-32 VDC) requires manual reset, and undervoltage shuts down below 21.6 VDC.