ADV141 Yokogawa CENTUM VP Digital Input Module
ADV141 Yokogawa CENTUM VP Digital Input Module
ADV141 Yokogawa CENTUM VP Digital Input Module
/ 3

ADV141 Yokogawa CENTUM VP Digital Input Module

  • Manufacturer: Yokogawa

  • Part Number: ADV141

  • Condition:New with Original Package

  • Product Type: Digital Input Modules

  • Country of Origin: Japan

  • Payment:T/T, Western Union

  • Shipping port: Xiamen

  • Warranty: 12 months

Yokogawa ADV141 Digital Input Modules

The Yokogawa ADV141-P00, also cataloged as the ADV141 Digital Input Module, operates as a dedicated hardware component for processing 100-120 V AC status and pushbutton signals within Yokogawa CENTUM CS and CENTUM VP control systems.

Hardware Specifications

Parameter Specification
Model ADV141 (Variant: ADV141-P00)
Brand Yokogawa
Origin Japan
Weight 0.3 kg
Dimensions 25 mm x 203 mm x 152 mm
Operating Temp 0 to 55 deg C
Power Consumption 500 mA at 5 VDC
Input Channels 16 channels
Rated Input Voltage 100 to 120 V AC, 50/60 Hz
Input ON Voltage 80 to 132 V AC (113 to 187 V peak)
Input OFF Voltage <= 20 V AC (<= 28 V peak)
Typical Input Current 4.7 mA per channel at 120 V AC, 60 Hz
Channel Isolation Common minus side every 8 channels
Withstanding Voltage 2 kV AC for 1 minute (signal to system); 1.35 kV AC between commons
Input Response Time <= 160 ms for status input

Process Control & Channel-to-Channel Isolation Architecture

Yokogawa CENTUM distributed control systems utilize individual isolation groups across field input circuitry to eliminate ground potential loops in high-voltage AC signal paths. The module organizes its 16 AC input channels into isolated groups of 8 channels sharing a common minus rail, with individual optical isolation arrays separating high-voltage field wiring from 5 VDC backplane logic. The signal processing network provides galvanic withstand capabilities up to 2 kV AC for 1 minute between field terminals and system logic, preventing field-side voltage transients from damaging central processor units.

Frequently Asked Questions

Q: What interconnect hardware bridges field signals to the module?

A: Field connections route either through direct pressure-clamp terminal blocks or via dedicated AKB332 cable assemblies.

Q: Can this module be deployed in a dual-redundant configuration?

A: Yes, two ADV141 modules support installation in adjacent slots on a dual-redundant baseplate to ensure uninterrupted signal acquisition.

Q: What is the maximum switching frequency supported for pushbutton inputs?

A: The input channel supports a maximum ON/OFF cycle frequency of 2.5 Hz with a minimum required ON detection time of 200 ms for pushbutton inputs.

Field Installation Guidelines

Ensure main power and AC field loops are de-energized prior to inserting or removing the module from the baseplate to prevent electrical shock.

Maintain physical separation between 100-120 V AC field wiring and low-voltage DC communication lines inside enclosure wireways. Route all external connections through AKB332 cables or secure individual leads into pressure-clamp terminals according to terminal group assignments.

Verify that subrack latching mechanisms lock securely upon module insertion to guarantee solid contact with backplane power and communication rails.