Yokogawa ADV142-P03 Digital Input Module
The Yokogawa ADV142-P03 is a 16-channel isolated AC digital input module designed for Yokogawa CENTUM VP and ProSafe-RS control systems within the FIO I/O family. Operating at nominal input voltages of 200 to 240 V AC (50/60 Hz), it converts high-voltage discrete AC signals from field switches, contactors, and process equipment into system logic states for automation and monitoring.
Input Characteristics and Functional Modes
The module accepts AC input voltages with an ON threshold range of 160 to 264 V AC peak and an OFF threshold of 40 V AC peak or less. It supports standard status input with a response time of 160 ms or less, as well as a pushbutton function enabled by the -P suffix for edge counting. In pushbutton mode, the input provides a minimum ON detection time of 200 ms and accommodates switching frequencies up to 2.5 Hz.
Isolation and System Protection
Electrical isolation is structured with commons shared every 8 channels. The insulation design provides a withstand voltage of 2 kV AC between input signals and system logic for 1 minute, along with 1.35 kV AC isolation between commons. The 03 suffix specifies ISA Standard G3 conformal coating for harsh environmental conditions and an extended operating temperature range of -20 deg C to 70 deg C.
Technical Specifications
| Parameter | Specification |
|---|---|
| Model | ADV142-P03 |
| Brand | Yokogawa |
| Product Type | Digital Input Modules |
| Product Series | Yokogawa FIO |
| Number of Channels | 16 channels |
| Rated Input Voltage | 200 to 240 V AC, 50/60 Hz |
| Input ON Voltage | 160 to 264 V AC (peak) |
| Input OFF Voltage | 40 V AC or less (peak) |
| Input Current | 6.2 mA typical per channel at 240 V AC / 60 Hz; 9.3 mA max |
| Status Input Response Time | 160 ms or less |
| Pushbutton Input Specs | Min ON detection time 200 ms; max cycle 2.5 Hz |
| Isolation Structure | Common shared every 8 channels |
| Withstand Voltage | 2 kV AC between signal and system for 1 min; 1.35 kV AC between commons for 1 min |
| Current Consumption | 500 mA max at 5 V DC |
| Conformal Coating | ISA Standard G3 (Option 03) |
| Operating Temperature | -20 deg C to 70 deg C |
| Dimensions | 107.5 x 130 x 32.8 mm |
| Weight | 0.3 kg |
Frequently Asked Questions
Q: What voltage levels does the ADV142-P03 process? A: It is designed for high-voltage AC discrete inputs operating at a rated nominal voltage of 200 to 240 V AC (50/60 Hz), with an ON detection band between 160 V AC and 264 V AC.
Q: What environmental options are included in the -P03 suffix? A: The 03 suffix specifies ISA Standard G3 conformal coating protection against corrosive atmospheres and extends the operating temperature rating from -20 deg C to 70 deg C.