ADV151-P50/D5A00 Yokogawa 32-Channel Digital Input Module
ADV151-P50/D5A00 Yokogawa 32-Channel Digital Input Module
ADV151-P50/D5A00 Yokogawa 32-Channel Digital Input Module
/ 3

ADV151-P50/D5A00 Yokogawa 32-Channel Digital Input Module

  • Manufacturer: Yokogawa

  • Part Number: ADV151-P50/D5A00

  • Condition:New with Original Package

  • Product Type:

  • Country of Origin: Japan

  • Payment:T/T, Western Union

  • Shipping port: Xiamen

  • Warranty: 12 months

Yokogawa ADV151-P50/D5A00 Digital Input Module

Configured for high-density discrete signal acquisition in CENTUM VP and ProSafe-RS control systems, the Yokogawa ADV151-P50/D5A00 (ADV151 Digital Input Module) provides direct physical/electrical execution. This module monitors 32 isolated 24 VDC input channels divided into two 16-channel common segments, capturing field states from limit switches, pushbuttons, and interlock contacts. It features dynamic Sequence of Events (SOE) time-stamping capability, dual-module redundancy support, and an integrated ATD5A-00 KS Cable Interface Adapter for system cable termination.

Suffix Breakdown & Model Matrix

Code / Suffix Designation Technical Description
ADV151 Base Model Digital Input Module (32-channel, 24 VDC, Isolated)
-P Suffix Code 1 With pushbutton input function
5 Suffix Code 2 Without status display; with no explosion protection
0 Suffix Code 3 Basic hardware type
/D5A00 Option Code Includes KS Cable Interface Adapter for 32-channel digital signals (Model: ATD5A-00)

Hardware Specifications

Parameter Specification
Model ADV151-P50/D5A00
Brand Yokogawa
Origin Japan
Weight 0.30 kg (Shipping weight: 1.50 kg to 3.00 kg)
Dimensions 107.5 x 130 x 32.8 mm
Operating Temp 0 to 60 deg C
Power Consumption 500 mA at 5 VDC
Channel Count 32 isolated input channels
Rated Input Voltage 24 VDC (Sink/Source)
Logical ON / OFF Voltages ON: 18.0 to 26.4 VDC; OFF: <= 5.0 VDC
Input Current ~4.1 mA +/- 20% per channel at rated voltage
Isolation Withstanding 2 kV AC between signal and system (1 min); 500 VAC between commons (1 min)
Scan Response Time <= 8 ms (Status input processing)

Channel Isolation and HART Loop Integrity

The Yokogawa ADV151-P50/D5A00 incorporates robust galvanic isolation layers engineered to maintain signal integrity across harsh processing plant environments. By providing 500 VAC isolation between its two 16-channel common groups and 2 kV AC isolation between field signals and the system backplane, the module prevents ground loops and electrical transients from propagating into central CPU processors. In complex DCS architectures, this isolation design operates in tandem with external 4-20 mA HART loop protocols and digital I/O networks to ensure that field-side short circuits or high-voltage surges do not degrade system availability or cause cross-channel interference.

Frequently Asked Questions

Q: How does the module handle dual-redundant configurations in the field slot?

A: Installing two ADV151 modules in adjacent redundant slots allows parallel signal processing, where both units simultaneously process field contacts and maintain uninterrupted control system feedback if one module fails.

Q: What termination hardware attaches to the /D5A00 option variant?

A: The /D5A00 suffix equips the module with an attached ATD5A-00 adapter unit, facilitating direct connection to Yokogawa dedicated AKB331 multi-core cables and signal terminal boards.

Q: Can the ADV151-P50/D5A00 accept field inputs above 24 VDC?

A: The module accepts continuous operating voltages up to 26.4 VDC in the logical ON range, with an absolute maximum allowable input limit of 30.0 VDC before triggering overvoltage protection limits.

Field Installation Guidelines

Mount the ADV151-P50/D5A00 securely into its assigned node unit slot on the FIO backplane, engaging the locking mechanism until it seats completely. Connect the AKB331 cable directly to the ATD5A-00 adapter interface, tightening all retaining fasteners to preserve physical contact stability during ambient cabinet vibration. Route external 24 VDC field power conductors through dedicated wire runs separate from high-voltage AC lines to mitigate electromagnetic interference. Ground the cable shield at a single, dedicated point on the system earth bar, ensuring proper single-point grounding. Verify that all field screw terminals achieve a solid mechanical connection with at least 5 full threads engaged prior to powering up the system cabinet.