Allen-Bradley 1756-OF8 ControlLogix Analog Output Module
Manufacturer: Allen-Bradley
-
Part Number: 1756-0F8
Condition:New with Original Package
Product Type: Analog Output Modules
-
Country of Origin: Sweden
Payment:T/T, Western Union
Shipping port: Xiamen
Warranty: 12 months
Allen-Bradley 1756-OF8 ControlLogix Analog Output Module
The Allen-Bradley 1756-OF8 is an 8-channel analog output module designed for the Rockwell Automation ControlLogix programmable automation controller platform. It converts digital values from the processor into configurable current (0-20 mA) or voltage (+/-10 VDC) signals to drive field actuators, control valves, and variable frequency drives.
Output Configuration and Diagnostics
Using an R-Ladder DAC conversion architecture, the module supports both left-justified 2's complement integer mode and IEEE 32-bit floating-point data formats. Each channel can be configured independently for voltage or current operation, providing 15-bit resolution in voltage mode and 16-bit resolution in current mode (Series B/C; 15-bit on Series A).
Built-in field protection includes 24 VDC overvoltage protection, current-mode open-circuit detection, and short-circuit current limiting to 21 mA or less. The module provides 50 V continuous output-to-backplane isolation, though channels share a common return without individual channel-to-channel isolation.
Chassis Installation and Wiring
The 1756-OF8 mounts directly into a single slot of a ControlLogix 1756 chassis and requires a 20-pin removable terminal block (RTB) for field wiring, specifically the 1756-TBNH or 1756-TBSH. Backplane power draw varies by hardware revision, requiring 140 mA at 5 V and 210 mA at 24 V for Series A, or 200 mA at 5.1 VDC and 300 mA at 24 VDC for Series B and C.
| Parameter | Specification |
|---|---|
| Model | 1756-OF8 |
| Brand | Allen-Bradley (Rockwell Automation) |
| Product Series | ControlLogix |
| Product Type | Analog Output Module |
| Number of Channels | 8 (voltage or current) |
| Output Current Range | 0-20 mA |
| Output Voltage Range | +/-10 VDC |
| Resolution | 15-bit (Series A); 15-bit voltage / 16-bit current (Series B/C) |
| Data Format | Integer mode (left-justified 2's complement), IEEE 32-bit floating point |
| Conversion Method | R-Ladder DAC, monotonic with no missing codes |
| Open Circuit Detection | Current mode only |
| Short Circuit Protection | Limited to 21 mA or less |
| Overvoltage Protection | 24 VDC |
| Isolation Voltage | 50 V continuous (output-to-backplane; no channel-to-channel isolation) |
| Backplane Current (5 V / 5.1 VDC) | 140 mA (Series A); 200 mA (Series B/C) |
| Backplane Current (24 VDC) | 210 mA (Series A); 300 mA (Series B/C) |
| Power Dissipation | 4.9 W at 60 deg C |
| Compatible Terminal Blocks | 1756-TBNH, 1756-TBSH (20-pin) |
| Operating Temperature | 0 deg C to +60 deg C |
| Dimensions (H x W x D) | 145 mm x 35 mm x 140 mm |
| Weight | 0.45 kg (1.0 lbs) |
| Certifications | CE, UL, CSA, Class I Division 2 |
| Country of Origin | USA |
Frequently Asked Questions
Q: Which removable terminal blocks are required for the Allen-Bradley 1756-OF8? A: Field wiring connects through a 20-pin ControlLogix removable terminal block, using either the 1756-TBNH (NEMA screw clamp) or the 1756-TBSH (spring clamp).
Q: Does the 1756-OF8 provide electrical isolation between individual output channels? A: No, the module provides 50 V continuous isolation between the output group and the chassis backplane, but it does not have channel-to-channel isolation.
Q: How do hardware revisions affect the backplane current and resolution of the 1756-OF8? A: Series A modules feature 15-bit resolution and draw 140 mA at 5 V and 210 mA at 24 V, whereas Series B and C revisions provide 16-bit current resolution (15-bit voltage) and draw 200 mA at 5.1 VDC and 300 mA at 24 VDC.