Bently Nevada 200200-06-06-05 Dual-Input Condition Monitoring Module
/ 1

Bently Nevada 200200-06-06-05 Dual-Input Condition Monitoring Module

  • Manufacturer: Bently Nevada

  • Part Number: 200200-06-06-05

  • Condition:New with Original Package

  • Product Type: Dual-Input Condition Monitoring Module

  • Country of Origin: USA

  • Payment:T/T, Western Union

  • Shipping port: Xiamen

  • Warranty: 12 months

 Bently Nevada 200200-06-06-05 – Dual-Input proTIM-R Module

Overview

The Bently Nevada 200200-06-06-05 is a dual-input proTIM-R module designed for seamless integration into the Trendmaster® Pro condition monitoring platform. It provides two independent channels that can be configured for either vibration or temperature measurement, enabling versatile deployment across industrial assets.

Each channel supports a wide range of sensors such as ICP® accelerometers, velocity transducers, K-type thermocouples, and Platinum RTDs. Its DIN rail mounting simplifies installation, while its rugged build ensures durability in harsh environments like refineries, power plants, and heavy manufacturing facilities.

Advanced signal conditioning—featuring Acceleration-to-Velocity (A-V) conversion and Acceleration Enveloping (AE)—allows engineers to capture both low-frequency and high-frequency fault data with high accuracy. This capability makes the module a key component for predictive maintenance programs.

 Technical Specifications

Feature Specification
Model Number 200200-06-06-05
Manufacturer Bently Nevada (a Baker Hughes company)
Series Trendmaster® Pro
Measurement Channels 2 independent, configurable
Supported Inputs A-V, AE, RTDs, Thermocouples
Sensor Compatibility ICP® accelerometers, velocity sensors, K-type thermocouples, Platinum RTDs
Signal Conditioning Acceleration-to-Velocity, Acceleration Enveloping
Frequency Response 10 Hz to 1 kHz (typical for vibration inputs)
AE Input Frequency Up to 10 kHz
Operating Temperature –20°C to +65°C
Power Supply 24 V DC
Mounting DIN rail
Communication RS-485 (Trendmaster® Pro network)
Electrical Isolation Yes, for all input channels

 