{"product_id":"bmxddi6402kru-schneider-electric-modicon-x80-digital-input-module","title":"BMXDDI6402KRU Schneider Electric Modicon X80 Digital Input Module","description":"\u003ch2\u003eSchneider Electric BMXDDI6402KRU Modicon X80 Discrete Input Module\u003c\/h2\u003e\n\u003cp\u003eThe \u003cstrong\u003eSchneider Electric BMXDDI6402KRU\u003c\/strong\u003e is a 64-channel positive-logic (sink) discrete digital input module for the Modicon X80 platform. Rated for 24 V DC nominal input (19-30 V DC operating range) with 0.6 mA input current and 4 ms typical response time, it connects via two 40-pin connectors and serves as a ruggedized variant in the series.\u003c\/p\u003e\n\u003ch3\u003eInput Channels, Thresholds, and Sensors\u003c\/h3\u003e\n\u003cp\u003eSixty-four isolated sink inputs accept 24 V DC signals from switches, field contacts, and 2-wire or 3-wire proximity sensors conforming to IEC 60947-5-2 and IEC 61131-2. Each channel presents a 40 kOhm input impedance and draws 0.6 mA at rated conditions.\u003c\/p\u003e\n\u003cp\u003eLogic state recognition is defined at \u0026gt;= 15 V DC for State 1 and \u0026lt;= 4 V DC for State 0, with a 4 ms typical and 7 ms maximum response time. Input paralleling is not supported on this module.\u003c\/p\u003e\n\u003ch3\u003eIsolation, Protection, and Mechanical Ratings\u003c\/h3\u003e\n\u003cp\u003eElectrical isolation between field wiring and internal controller logic is supported by greater than 10 MOhm insulation resistance at 500 V DC. External protection specifies a 0.5 A fast-blow fuse per channel group, while internal logic draw is 160 mA at 3.3 V DC with 4.3 W power dissipation.\u003c\/p\u003e\n\u003cp\u003eThe enclosure provides IP20 protection, weighs approximately 0.145 kg, and uses two 40-pin connectors for high-density field wiring.\u003c\/p\u003e\n\u003ch3\u003eTechnical Specifications\u003c\/h3\u003e\n\u003cfigure class=\"table\"\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr\u003e\n\u003cth\u003e\u003cstrong\u003eParameter\u003c\/strong\u003e\u003c\/th\u003e\n\u003cth\u003e\u003cstrong\u003eSpecification\u003c\/strong\u003e\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003eModel\u003c\/td\u003e\n\u003ctd\u003eBMXDDI6402KRU\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eBrand\u003c\/td\u003e\n\u003ctd\u003eSchneider Electric\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eSeries\u003c\/td\u003e\n\u003ctd\u003eModicon X80\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eProduct Type\u003c\/td\u003e\n\u003ctd\u003eDiscrete Digital Input Module\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eNumber of Inputs\u003c\/td\u003e\n\u003ctd\u003e64\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eInput Type\u003c\/td\u003e\n\u003ctd\u003eIsolated digital inputs\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eInput Logic\u003c\/td\u003e\n\u003ctd\u003ePositive logic (sink)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eRated Input Voltage\u003c\/td\u003e\n\u003ctd\u003e24 V DC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eInput Voltage Range\u003c\/td\u003e\n\u003ctd\u003e19-30 V DC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eInput Current\u003c\/td\u003e\n\u003ctd\u003e0.6 mA per input\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eInput Impedance\u003c\/td\u003e\n\u003ctd\u003e40 kOhm\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eVoltage State 1\u003c\/td\u003e\n\u003ctd\u003e\u0026gt;= 15 V DC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eVoltage State 0\u003c\/td\u003e\n\u003ctd\u003e\u0026lt;= 4 V DC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eTypical Response Time\u003c\/td\u003e\n\u003ctd\u003e4 ms\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eMaximum Response Time\u003c\/td\u003e\n\u003ctd\u003e7 ms\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eInput Paralleling\u003c\/td\u003e\n\u003ctd\u003eNot supported\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eSensor Compatibility\u003c\/td\u003e\n\u003ctd\u003e2-wire \/ 3-wire proximity sensors\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eSensor Standards\u003c\/td\u003e\n\u003ctd\u003eIEC 60947-5-2, IEC 61131-2\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eExternal Protection\u003c\/td\u003e\n\u003ctd\u003e0.5 A fast-blow fuse per channel group\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eConnection Type\u003c\/td\u003e\n\u003ctd\u003eTwo 40-pin connectors\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eProtection Rating\u003c\/td\u003e\n\u003ctd\u003eIP20\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eTypical Current Consumption\u003c\/td\u003e\n\u003ctd\u003e160 mA at 3.3 V DC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003ePower Dissipation\u003c\/td\u003e\n\u003ctd\u003e4.3 W\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eInsulation Resistance\u003c\/td\u003e\n\u003ctd\u003eGreater than 10 MOhm at 500 V DC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eNet Weight\u003c\/td\u003e\n\u003ctd\u003e0.145 kg\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003c\/figure\u003e\n\u003ch3\u003eFrequently Asked Questions\u003c\/h3\u003e\n\u003cp\u003eQ: What voltage thresholds define logic State 1 and State 0 on the \u003cstrong\u003eBMXDDI6402KRU\u003c\/strong\u003e? A: State 1 is recognized at \u0026gt;= 15 V DC and State 0 at \u0026lt;= 4 V DC, operating within a 19-30 V DC input voltage range.\u003c\/p\u003e\n\u003cp\u003eQ: Can input channels on the \u003cstrong\u003eBMXDDI6402KRU\u003c\/strong\u003e be paralleled? A: No, input paralleling is not supported, and external circuit protection requires a 0.5 A fast-blow fuse per channel group.\u003c\/p\u003e\n\u003cp\u003eQ: What sensor types are listed for compatibility with the \u003cstrong\u003eBMXDDI6402KRU\u003c\/strong\u003e? A: It supports 2-wire and 3-wire proximity sensors under IEC 60947-5-2 and IEC 61131-2 requirements.\u003c\/p\u003e","brand":"Schneider","offers":[{"title":"Default Title","offer_id":67994400456803,"sku":"BMXDDI6402KRU","price":267.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0583\/5246\/8067\/files\/412._bd19b702-a42f-4968-aecf-c51b01887eff.jpg?v=1795422566","url":"https:\/\/www.autocontrolglobal.com\/products\/bmxddi6402kru-schneider-electric-modicon-x80-digital-input-module","provider":"AutoControl Global","version":"1.0","type":"link"}