BMXDRC0805 Schneider Electric Modicon X80 Discrete Output Module
Manufacturer: Schneider
-
Part Number: BMXDRC0805
Condition:New with Original Package
Product Type: Discrete Output Modules
-
Country of Origin: USA
Payment:T/T, Western Union
Shipping port: Xiamen
Warranty: 12 months
Schneider Electric BMXDRC0805 Modicon X80 Relay Output Module
The Schneider Electric BMXDRC0805 is an 8-channel discrete relay output module designed for the Modicon X80 PLC platform. It provides isolated normally open (NO) and normally closed (NC) relay contact outputs operating across wide voltage ranges of 19 to 264 VAC and 5 to 150 VDC. This module allows the PLC to control field devices such as contactors, solenoid valves, and industrial actuators with configurable positive or negative output logic.
Electrical Characteristics and Load Ratings
The module interfaces via a 40-way terminal block and provides galvanic isolation with insulation resistance exceeding 10 MΩ at 500 VDC. Output switching speed is specified with an activation time under 10 ms and a deactivation time under 13 ms.
Thermal switching capability varies with ambient operating conditions to prevent thermal stress on internal components:
- 4 A continuous free-air thermal current per point at 40 deg C
- 3 A continuous free-air thermal current per point at 50 deg C
- 2 A continuous free-air thermal current per point at 60 deg C
Minimum switching requirements mandate at least 10 mA at 5 VDC to ensure reliable contact clean-up and signal continuity.
Technical Specifications
| Parameter | Specification |
|---|---|
| Model | BMXDRC0805 |
| Brand | Schneider Electric |
| Series | Modicon X80 |
| Product Type | Discrete Relay Output Module |
| Number of Outputs | 8 channels |
| Output Type | Isolated relay (NO / NC) |
| Output Logic | Positive or negative |
| Rated AC Voltage | 24-240 VAC (19-264 VAC operating range) |
| Rated DC Voltage | 24-125 VDC (5-150 VDC operating range) |
| Network Frequency | 50/60 Hz (47-63 Hz limits) |
| Electrical Connection | 40-way terminal block |
| Minimum Switching Load | 10 mA at 5 VDC |
| Response Time | <= 10 ms (activation), <= 13 ms (deactivation) |
| Thermal Current (Ith) | 4 A at 40 deg C, 3 A at 50 deg C, 2 A at 60 deg C |
| Power Dissipation | 3.6 W |
| Current Consumption | 40 mA at 3.3 VDC, 101 mA at 24 VDC |
| Insulation Resistance | > 10 MOhm at 500 VDC |
| Operating Temperature | 0 to 60 deg C |
| Mounting Platform | Modicon X80 rack |
| Standards Compliance | EN/IEC 61131-2 |
Frequently Asked Questions
Q: What are the current derating thresholds for the BMXDRC0805 outputs based on temperature? A: The module supports up to 4 A per channel at 40 deg C, which derates to 3 A at 50 deg C and 2 A at 60 deg C.
Q: What is the minimum switching load required for accurate contact operation? A: The minimum switching requirement is 10 mA at 5 VDC to guarantee reliable contact switching.