CC-TDIL01 Honeywell Experion Series C Digital Input IOTA
CC-TDIL01 Honeywell Experion Series C Digital Input IOTA
CC-TDIL01 Honeywell Experion Series C Digital Input IOTA
/ 3

CC-TDIL01 Honeywell Experion Series C Digital Input IOTA

  • Manufacturer: Honeywell

  • Part Number: CC-TDIL01

  • Condition:New with Original Package

  • Product Type: Digital Input Modules

  • Country of Origin: USA

  • Payment:T/T, Western Union

  • Shipping port: Xiamen

  • Warranty: 12 months

Honeywell CC-TDIL01 Experion PKS Series C Digital Input IOTA

Configured for discrete field signal acquisition in Honeywell Experion PKS platforms, the Honeywell CC-TDIL01 (CC-TDIL01) Digital Input Input/Output Terminal Assembly provides direct physical/electrical execution.

Hardware Specifications

Parameter Specification
Model CC-TDIL01 / 51308386-175
Brand Honeywell
Origin USA
Weight 0.45 kg
Dimensions 127 mm x 89 mm x 32 mm
Operating Temp -20 to 60 deg C
Power Consumption 24 VDC nominal supply (18 to 30 VDC range)
System Platform Honeywell Experion PKS / C300 Series C
Number of Input Channels 32 channels
Signal Range 0 to 30 VDC (On-State >= 12 VDC, Off-State <= 5 VDC)
Input Current Draw 7 to 10 mA per channel
Galvanic Isolation Channel-to-channel and channel-to-system isolation
Circuit Protection Internal field-wiring short-circuit protection
Compatible Modules CC-PDIL01 / CC-PDIS01
Mounting Format 9-inch Series C IOTA carrier rack

4-20 mA HART Loop Protocol & Channel Isolation

Engineers integrate the assembly into distributed control networks requiring strict separation between high-voltage field wiring and sensitive processor buses. Channel-to-channel galvanic isolation blocks high common-mode voltage spikes and suppresses electromagnetic noise in high-density panel configurations. The board supports selectable internal or external 24 VDC field sensing power, while internal diagnostic circuitry continuously evaluates terminal state transitions and flags wiring shorts before loop power failure occurs.

Frequently Asked Questions

Q: Does the CC-TDIL01 require a companion electronic module to process digital inputs?

A: Yes, the unit functions as a terminal assembly and must be paired with a CC-PDIL01 standard digital input module or a CC-PDIS01 Sequence-of-Events (SOE) module.

Q: How does the hardware distinguish between ON and OFF signal states?

A: Channel circuitry registers an ON state when field voltage reaches or exceeds 12 VDC, and registers an OFF state when voltage drops to or below 5 VDC.

Q: Can field channels be powered via external voltage sources?

A: Yes, the IOTA hardware jumpers allow configuration for either internal bus-supplied 24 VDC sensing or external field power loop excitation.

Field Installation Guidelines

Mount the assembly onto the 9-inch Series C carrier rack inside a grounded control enclosure. Ensure a minimum vertical clearance of 50 mm surrounding the board to support natural convection cooling up to the 60 deg C operating threshold. Connect incoming field wiring to the designated terminal block screw pairs, torquing screws to 0.5 Nm. Route signal lines separately from high-voltage AC cables and ground all shielded cables directly to the enclosure earth bus bar to eliminate noise coupling.