CE4003S2B1 Emerson DeltaV S-Series 8-Channel Analog Input Module
CE4003S2B1 Emerson DeltaV S-Series 8-Channel Analog Input Module
CE4003S2B1 Emerson DeltaV S-Series 8-Channel Analog Input Module
/ 3

CE4003S2B1 Emerson DeltaV S-Series 8-Channel Analog Input Module

  • Manufacturer: Emerson

  • Part Number: CE4003S2B1

  • Condition:New with Original Package

  • Product Type: Analog Input Modules

  • Country of Origin: USA

  • Payment:T/T, Western Union

  • Shipping port: Xiamen

  • Warranty: 12 months

Emerson CE4003S2B1 DeltaV Analog Input Module

Configured for 4-20 mA field signal acquisition in DeltaV S-series networks, the Emerson CE4003S2B1 (CE4003S2B1 Analog Input Module) provides direct physical/electrical execution. The module converts analog process variables from field transmitters into 16-bit digital values, routing real-time data across the DeltaV local bus interface for centralized process control.

Hardware Specifications

Parameter Specification
Model CE4003S2B1
Brand Emerson
Origin USA
Weight 0.18 kg
Dimensions 51 x 102 x 102 mm
Operating Temp -40 to +70 deg C
Power Consumption LocalBus: 12 VDC at 150 mA
Input Channels 8 isolated analog inputs
Signal Range 4-20 mA
Resolution 16-bit analog-to-digital conversion
HART Protocol Support Pass-through, point-to-point
Field Power Ratings Bussed Field Power: 12 VDC at 300 mA; Field Circuit: 24 VDC at 32 mA
Storage Temperature -40 to +85 deg C
Relative Humidity 5% to 95% non-condensing
Environmental Ratings Airborne Contaminants ISA-S71.04 Class G3, IP20
Mechanical Resistance Shock: 10 g half-sine wave for 11 ms; Vibration: 1 mm peak-to-peak (2-13.2 Hz), 0.7 g (13.2-150 Hz)
Hazardous Location Ratings CE, UL, ATEX, IECEx (Zone 2 / Class I Div 2)

4-20 mA HART Loop Protocol and Channel Isolation

The CE4003S2B1 module incorporates channel-to-channel galvanic isolation across all 8 input paths, eliminating ground loop currents and suppressing common-mode electrical noise in distributed field wiring. Onboard signal processing circuitry supports the 4-20 mA HART loop protocol via point-to-point pass-through mode. This architecture enables secondary HART digital signals, including device diagnostics and calibration parameters, to pass directly to plant management software without disrupting primary analog measurement loops.

Frequently Asked Questions

Q: Does the CE4003S2B1 module allow online removal and insertion under system power?

A: Yes. The module supports live installation and removal on powered DeltaV S-series carriers without disrupting backplane communications or damaging adjacent I/O cards.

Q: How does the module maintain measurement integrity across noisy field lines?

A: Channel-to-channel galvanic isolation isolates each loop from adjacent noise coupling, while the 16-bit digitizer filters high-frequency transient interference.

Q: What are the cabinet enclosure requirements for ATEX or IECEx Zone 2 hazardous locations?

A: The module must be housed in an enclosure rated to at least IP54 or equivalent protection to prevent dust and ingress, following Zone 2 wiring standards.

Field Installation Guidelines

Align the CE4003S2B1 module with the slot keying on the DeltaV S-series carrier and press firmly until the locking latch engages the backplane connector. Fasten field wiring to the corresponding terminal block, keeping 4-20 mA current cables physically isolated from AC power conductors to limit electromagnetic interference. Bond field cable shields at the cabinet ground bar using a single-point connection. Before powering the system, ensure the cabinet structure provides adequate heat dissipation to support the -40 to +70 deg C operating temperature range.

You may also like