CI854BK01 ABB PROFIBUS-DP Interface Module AC 800M Communication
Manufacturer: ABB
-
Part Number: CI854BK01 3BSE069449R1
Condition:New with Original Package
Product Type: Communication Modules
-
Country of Origin: Sweden
Payment:T/T, Western Union
Shipping port: Xiamen
Warranty: 12 months
ABB CI854BK01 PROFIBUS-DP/V1 Interface Module
Configured for high-speed fieldbus integration within ABB AC 800M control systems, the ABB CI854BK01 (CI854B PROFIBUS-DP/V1 Interface Module) provides direct physical and electrical execution of PROFIBUS-DP/V1 communication protocols.
Hardware Specifications
| Parameter | Specification |
|---|---|
| Model | CI854BK01 |
| Brand | ABB |
| Origin | Sweden |
| Weight | 0.7 kg (Module) |
| Dimensions | 186 mm x 59 mm x 127.5 mm |
| Operating Temp | +5 to +55 deg C |
| Power Consumption | 190 mA at 24 VDC |
| Protocol | PROFIBUS DP-V1 |
| Transmission Speed | 9.6 to 12,000 kbit/s |
| Connector Type | DB-9 Female |
| Protection Class | IP20 |
Deterministic Network Connectivity
The CI854BK01 utilizes high-speed PROFIBUS-DP architecture to ensure deterministic data exchange between the AC 800M controller and remote field devices. To maintain network integrity, the PROFIBUS segment requires active termination at the two physical ends of the transmission line. The firmware supports advanced diagnostic functions compatible with ABB 800xA 6.0.3.2 and Compact Control Builder environments. When integrated within high-availability configurations, the module manages CEXbus communication velocity and supports seamless master redundancy transitions when paired with a secondary module.
Frequently Asked Questions
Q: Does the module support hot-swap functionality during active process operation?
A: Yes, the CI854B supports hot-swap capability, allowing for module replacement without requiring a complete system shutdown, provided the baseplate connection remains stable.
Q: How is line redundancy achieved using this module?
A: Line redundancy is implemented by utilizing the two integrated PROFIBUS ports on the module to connect to distinct segments of the PROFIBUS network.
Q: What are the primary considerations for master redundancy configuration?
A: Master redundancy requires two CI854B modules configured within the controller project. Ensure the CEXbus interconnections are correctly seated to allow for the automated synchronization of mastership between the primary and backup modules.
Field Installation Guidelines
- Mounting: Ensure the TP854 baseplate is securely fastened to a standard symmetrical DIN rail. Verify the mechanical locking mechanism is fully engaged before installing the CI854B module.
- Grounding and Shielding: To mitigate electromagnetic interference (EMI), ensure the PROFIBUS cable shield is properly terminated to a low-impedance earth connection at the cabinet entry point.
- Termination: Use connectors with integrated switchable termination resistors at the extreme ends of the PROFIBUS segment. Ensure these connectors receive 5 VDC power from the bus to maintain signal amplitude.
- Environment: Maintain the installation within an IP20-rated enclosure to meet the specified G3 corrosion protection standards (ISA 71.04). Ensure adequate clearance for convective cooling to prevent internal heat accumulation exceeding the +55 deg C limit.