Digital Input Module | YOKOGAWA ADV151-P13 S2
Digital Input Module | YOKOGAWA ADV151-P13 S2
Digital Input Module | YOKOGAWA ADV151-P13 S2
/ 3

Digital Input Module | YOKOGAWA ADV151-P13 S2

  • Manufacturer: Yokogawa

  • Part Number: ADV151-P13 S2

  • Condition:New with Original Package

  • Product Type: Digital Input Modules

  • Country of Origin: Japan

  • Payment:T/T, Western Union

  • Shipping port: Xiamen

  • Warranty: 12 months

YOKOGAWA ADV151-P13 S2 Digital Input Module

The YOKOGAWA ADV151-P13 S2 serves as the primary ADV151 Digital Input Module utilized to execute discrete ON/OFF signal acquisition across CENTUM VP, CS 3000, and CS 1000 platforms.

Hardware Specifications

Parameter Specification
Model ADV151-P13 S2
Brand YOKOGAWA
Origin Indonesia
Weight 0.45 kg (Shipping Weight: 1.5 kg)
Dimensions 81 x 103 x 146 mm
Operating Temp -20 to +70 deg C
Power Consumption 290 mA max (at 5 VDC), 140 mA max (at 24 VDC)
Channel Count 32 digital inputs
Input Signal Type No-voltage dry contact
Rated Input Voltage 24 VDC nominal
ON State Condition Less than or equal to 1 kOhm
OFF State Condition Greater than or equal to 100 kOhm
Input Current 6 mA +/- 20 percent (at 24 VDC, 0 Ohm)
Isolation Voltage 2 kV AC between input signal and system (1 min)
Response Time Less than or equal to 40 ms
Terminal Connection Pressure clamp terminal block or MIL connector
Hot Swap Capability Supported

Channel-to-Channel Isolation & Cold Junction Compensation

Field instrument signals enter the digital input circuitry through optocouplers that establish 2 kV AC galvanic isolation between input channels and internal system backplane logic. This isolation topology blocks common-mode voltage spikes and suppresses signal cross-talk across channels in noise-intensive industrial environments. While cold junction compensation (CJC) applies primarily to thermocouple analog loops, the discrete filtering architecture in this module suppresses high-frequency field contact chatter, maintaining stable discrete state logic transfers to the DCS CPU.

Frequently Asked Questions

Q: Can engineers hot-swap the module while system backplane power remains active?

A: Yes, the module supports live online hot-swapping inside standard I/O racks without interrupting communications or power distribution to adjacent operational modules.

Q: What action should plant technicians take if replacing an obsolete ADV151-P13 hardware module?

A: Yokogawa designates the ADV151-P63/D5A00 Digital Input Module as the direct factory replacement unit for legacy ADV151-P13 series hardware.

Field Installation Guidelines

Mount the module securely into its designated slot on the CENTUM system node I/O rack until the retaining latches lock into position. Route all field wiring through shielded twisted-pair cables, terminating the cable shields at a central low-impedance earth ground bar. When connecting field conductors to pressure clamp terminal assemblies or MIL connector cables, ensure clean wiring paths isolated from high-voltage AC lines to prevent electromagnetic noise induction.