Digital Input Module | Yokogawa NFDV151-P10 S
Manufacturer: Yokogawa
-
Part Number: NFDV151-P10 S
Condition:New with Original Package
Product Type: Digital Input Modules
-
Country of Origin: Japan
Payment:T/T, Western Union
Shipping port: Xiamen
Warranty: 12 months
YOKOGAWA NFDV151-P10 S Digital Input Module
The YOKOGAWA NFDV151-P10 S, also cataloged as the NFDV151-P10 Digital Input Module, operates as a dedicated hardware component for 32-channel 24 V DC digital signal acquisition within STARDOM FCN controller platforms.
Hardware Specifications
| Parameter | Specification |
|---|---|
| Model | NFDV151-P10 S |
| Brand | YOKOGAWA |
| Origin | Japan |
| Weight | 0.3 kg |
| Dimensions | 130 x 107.5 x 32.8 mm |
| Operating Temp | 0 deg C to 40 deg C |
| Power Consumption | Up to 500 mA at 5 V DC |
| Number of Input Channels | 32 channels |
| Rated Input Voltage | 24 V DC |
| Input Configuration | Sink / Source compatible |
| Input-to-System Isolation | 2,000 V AC withstand voltage |
Channel-to-Channel Isolation and Signal Conditioning
Engineered to maintain strict signal integrity within industrial control networks, this module features robust channel-to-channel isolation and 2,000 V AC input-to-system dielectric protection. The circuitry ensures reliable common-mode noise rejection across 16-channel groups while processing sink-type and source-type digital inputs without voltage degradation or cross-talk interference.
Frequently Asked Questions
Q: Does this digital input module support live hot-swapping on the controller backplane?
A: No. System power must be de-energized before inserting or unseating the module to prevent electrical damage to the internal bus connections.
Q: What is the maximum response time for status inputs processed through this module?
A: The status input response time is 8 ms or less, with a minimum push-button ON detection time of 20 ms.
Field Installation Guidelines
- Verify that controller rack power is completely shut off before handling the input module.
- Inspect the rear connector pins and front connection terminals for physical damage or contamination.
- Mount the module securely onto the designated slot, ensuring firm engagement with backplane guides.
- Connect external field wiring to the pressure-clamp terminal block or MIL connector cable while maintaining proper shield grounding.