Discrete Output Module GE IC693MDL752F Series 90-30
Discrete Output Module GE IC693MDL752F Series 90-30
Discrete Output Module GE IC693MDL752F Series 90-30
/ 3

Discrete Output Module GE IC693MDL752F Series 90-30

  • Manufacturer: GE Fanuc

  • Part Number: IC693MDL752F

  • Condition:New with Original Package

  • Product Type: Digital Output Cards

  • Country of Origin: USA

  • Payment:T/T, Western Union

  • Shipping port: Xiamen

  • Warranty: 12 months

GE Fanuc IC693MDL752F Series 90-30 Digital Output Module

The GE Fanuc IC693MDL752F, also cataloged as the IC693MDL752 DC Output Module, operates as a dedicated hardware component for direct physical switching of 12/24 VDC discrete loads within GE Fanuc Series 90-30 PLC platforms.

Hardware Specifications

Parameter Specification
Model IC693MDL752F (IC693MDL752)
Brand GE Fanuc
Origin USA
Weight 0.30 kg
Dimensions 41 x 140 x 127 mm
Operating Temp 0 to 60 deg C
Power Consumption 300 mA at +5 VDC (backplane bus current draw)
Output Points 32 points (2 isolated groups of 16)
Nominal Voltage 12/24 VDC (operating range 10.2 to 30 VDC)
Output Logic Positive logic (sourcing)
Continuous Current 0.5 A per point, 8 A max per group common
Inrush Current 1.0 A for 10 ms
Isolation 1500 VDC field-to-logic, 250 VAC group-to-group
Response Time 0.5 ms ON to OFF / OFF to ON

Backplane Bus Communication Velocity and Firmware Compatibility

The internal transistor switching architecture interfaces directly with the Series 90-30 rack backplane, transferring discrete status bits without reducing backplane bus communication velocity during high-density I/O scan cycles. Integrated optical isolators protect internal controller logic against voltage spikes and noise generated on field wiring lines. Full firmware flash compatibility across Series 90-30 CPU models ensures consistent register updating, real-time channel status LED mapping, and execution of fast-cycling output commands.

Frequently Asked Questions

Q: What are the primary electrical load limitations for each channel on the IC693MDL752F?

A: Each output channel supports a maximum continuous load current of 0.5 A at 30 VDC, while the combined load for each 16-point group common must not exceed 8 A.

Q: Does the IC693MDL752F require separate external power supplies for each output group?

A: Yes, because the module contains two electrically isolated groups of 16 points, each group requires its own external 12/24 VDC field power connection across its respective common terminal.

Field Installation Guidelines

Turn off all panel power before seating or removing the IC693MDL752F module from the Series 90-30 rack baseplate. Align the module card with the target slot rails, pushing firmly until the rear backplane connectors lock completely. Wire external 12/24 VDC power and field loads to the removable terminal block using copper conductors rated for panel ambient temperatures. Maintain physical separation between DC output control wiring and high-voltage AC lines to minimize inductive noise interference on logic signals.