DO890 ABB | S800 I/O Digital Output Module with IS Protection
DO890 ABB | S800 I/O Digital Output Module with IS Protection
DO890 ABB | S800 I/O Digital Output Module with IS Protection
/ 3

DO890 ABB | S800 I/O Digital Output Module with IS Protection

  • Manufacturer: ABB

  • Part Number: DO890

  • Condition:New with Original Package

  • Product Type: I/O Digital Output Module with IS Protection

  • Country of Origin: Sweden

  • Payment:T/T, Western Union

  • Shipping port: Xiamen

  • Warranty: 12 months

 Product Description

The ABB DO890, product ID 3BSC690074R1, is a 4-channel digital output module designed for ABB’s S800 I/O and System 800xA platforms. Each channel includes intrinsic safety protection, allowing direct connection to Ex-certified field devices in hazardous areas without external barriers.

The module delivers up to 40 mA to a 300 Ω load, making it ideal for driving solenoid valves, alarm sounders, and indicator lamps. Each channel also supports open and short circuit detection, and output and fault LEDs simplify maintenance. All four channels are galvanically isolated from each other, the ModuleBus, and the power supply. Power to the outputs is converted from the 24 V supply connections.

Technical Specifications

Specification Details
Model Number DO890
Product ID 3BSC690074R1
System Compatibility ABB S800 I/O, System 800xA
Output Channels 4 digital outputs
Output Type Current source
Nominal Output Voltage 11 V DC
Nominal Output Current 40 mA per channel
Load Resistance Range 150–5000 Ω
Fault Detection Open circuit & short circuit per channel
Isolation Galvanic isolation between channels, ModuleBus, and power supply
Status Indicators Output and fault LEDs per channel
Compatible Terminal Units TU890 (Ex applications), TU891 (non-Ex)
Dimensions (W × H × D) 45 mm × 119 mm × 102 mm
Weight 0.3 kg
Country of Origin Sweden
Application Areas Hazardous area control, industrial automation, solenoid/indicator driving

FAQ

Q1: Can the DO890 module be used in hazardous areas?
A1: Yes, each channel includes intrinsic safety protection for direct Ex-device connection.

Q2: What is the maximum current per channel?
A2: The DO890 drives up to 40 mA into a 300 Ω load per channel.

Q3: Are the channels isolated?
A3: Yes, all channels are galvanically isolated from each other, the ModuleBus, and the power supply.

Q4: Which field devices can it control?
A4: It drives Ex-certified solenoid valves, alarm sounders, and indicator lamps.

Q5: What terminal units are compatible?
A5: Use TU890 for Ex applications and TU891 for non-Ex applications.

 

You may also like