Emerson KJ3102X032 DeltaV 8-Channel Analog Input Module
Emerson KJ3102X032 DeltaV 8-Channel Analog Input Module
Emerson KJ3102X032 DeltaV 8-Channel Analog Input Module
/ 3

Emerson KJ3102X032 DeltaV 8-Channel Analog Input Module

  • Manufacturer: Emerson

  • Part Number: SE6101/VE4003S4B1

  • Condition:New with Original Package

  • Product Type: Analog Input Modules

  • Country of Origin: USA

  • Payment:T/T, Western Union

  • Shipping port: Xiamen

  • Warranty: 12 months

Emerson KJ3102X032 DeltaV Analog Input Module

The Emerson 12P1863X032, also cataloged as the KJ3102X032 Analog Input Module, operates as a dedicated hardware component for 4-20 mA field signal acquisition within Emerson DeltaV DCS platforms. The 8-channel board digitizes continuous process variables into 16-bit binary values, routing real-time data directly across the LocalBus backplane interface.

Hardware Specifications

Parameter Specification
Model 12P1863X032 / KJ3102X032
Brand Emerson
Origin USA
Weight 0.3 kg
Dimensions 51 x 102 x 102 mm
Operating Temp -40 to +70 deg C
Power Consumption LocalBus: 12 VDC at 150 mA
Input Channels 8 isolated analog inputs
Signal Range 4-20 mA current input
Resolution 16-bit analog-to-digital conversion
HART Protocol Support Pass-through, point-to-point only
Bussed Field Power Rating 12 VDC at 300 mA
Field Circuit Rating 24 VDC at 32 mA
Storage Temperature -40 to +85 deg C
Humidity Range 5% to 95% non-condensing
Mechanical Resistance Shock: 10 g half-sine wave for 11 ms; Vibration: 1 mm peak-to-peak (2-13.2 Hz), 0.7 g (13.2-150 Hz)
Protection & Contaminants IP20, ISA-S71.04 Class G3
Certifications CE, UL, ATEX, IECEx (Zone 2 / Class I Div 2)

4-20 mA HART Loop Protocol and Galvanic Isolation

The KJ3102X032 provides channel-to-channel galvanic isolation across all 8 input paths, blocking ground loop development and suppressing common-mode electrical interference across field wiring. Internal digital conversion circuitry supports 4-20 mA HART loop protocol pass-through communication in point-to-point topology. This capability allows secondary digital signals, device diagnostics, and calibration parameters to flow from smart field transmitters directly into plant management software without degrading the primary 16-bit analog value.

Frequently Asked Questions

Q: Can engineers remove and insert the KJ3102X032 module while the carrier is energized?

A: Yes. The hardware supports live removal and insertion under system power on powered DeltaV S-series carriers without corrupting backplane communication or damaging adjacent cards.

Q: How does the module handle high-frequency common-mode noise on long field wiring runs?

A: Channel-to-channel galvanic isolation decouples individual loops, while the 16-bit analog-to-digital converter employs digital filtering to suppress high-frequency transient interference.

Q: What are the enclosure specifications when deploying the module in Zone 2 environments?

A: Field installation requires mounting inside a cabinet rated to at least IP54 or equivalent ingress protection to comply with ATEX and IECEx Zone 2 requirements.

Field Installation Guidelines

Seat the KJ3102X032 module firmly into its designated slot on the DeltaV carrier until the mechanical latch secures the module to the backplane header. Connect field wiring to the corresponding terminal block, separating 4-20 mA current cables from high-voltage AC conductors to prevent inductive cross-talk. Terminate cable shielding at the primary enclosure grounding bus using a low-impedance single-point connection. Confirm that cabinet thermal management maintains ambient conditions within -40 to +70 deg C before supplying power to the LocalBus carrier.

You may also like