Emerson KL2101X1-BA1 12P4987X122 DeltaV Wireless I/O Card Module
Emerson KL2101X1-BA1 12P4987X122 DeltaV Wireless I/O Card Module
Emerson KL2101X1-BA1 12P4987X122 DeltaV Wireless I/O Card Module
/ 3

Emerson KL2101X1-BA1 12P4987X122 DeltaV Wireless I/O Card Module

  • Manufacturer: Emerson

  • Part Number: KL2101X1-BA1 12P4987X122

  • Condition:New with Original Package

  • Product Type: Wireless Modules

  • Country of Origin: USA

  • Payment:T/T, Western Union

  • Shipping port: Xiamen

  • Warranty: 12 months

Emerson KL2101X1-BA1 DeltaV Wireless I/O Card

The Emerson KL2101X1-BA1, also cataloged as the KL2101X1 Wireless I/O Card, operates as a dedicated hardware component for field signal integration within DeltaV Electronic Marshalling systems.

Hardware Specifications

Parameter Specification
Model KL2101X1-BA1 (Part Number: 12P4987X122)
Brand Emerson
Origin USA
Weight 0.8 kg
Dimensions 160 x 160 x 120 mm
Operating Temp -40 to +70 deg C
Power Consumption Input: 24 VDC at ~400 mA; Output: 24 VDC at ~100 mA
System Compatibility Emerson DeltaV Electronic Marshalling
Signal Types Supported Analog and Discrete field signals
Terminal Block Keying Position D2
Airborne Contaminants ISA-S71.04 Class G3
Shock Resistance 10 g half-sine wave for 11 ms
Vibration Resistance 1 mm peak-to-peak (2-13.2 Hz), 0.7 g (13.2-150 Hz)
Certifications ATEX, IECEx, FM, UKEX (Zone 2 / Class I Div. 2)

Process Control and Communication Isolation

The module communicates field data wirelessly while providing optical channel-to-channel isolation between internal processing circuits and external electrical interfaces. Integrated power regulators convert the primary 24 VDC input down to supply field loops, preventing ground loops across sensor wiring. The unit integrates with 4-20 mA HART loop protocol device networks, maintaining signal integrity and digital diagnostic transmission across the local control backplane.

Frequently Asked Questions

Q: What are the input and output electrical ratings for the KL2101X1-BA1 module?

A: The card accepts a 24 VDC primary power input drawing approximately 400 mA and outputs 24 VDC at up to 100 mA to power connected field interfaces.

Q: Does the KL2101X1-BA1 support hot-swappable installation on active carriers?

A: The module supports hot-swappable replacement on energized DeltaV baseplate slots, provided the terminal block keying matches Position D2 to prevent physical mis-insertion.

Field Installation Guidelines

  1. Verify that the carrier baseplate terminal block keying is set to Position D2 before inserting the module edge connector.
  2. Seat the module firmly onto the DeltaV carrier baseplate and engage the retaining screws to ensure proper backplane connection.
  3. Connect the cabinet ground strap to the designated shield terminal bar to minimize ambient RF noise and electromagnetic interference.
  4. Maintain minimum clearances from high-voltage cables and metallic obstructions around the wireless interface to prevent signal attenuation.
You may also like