Emerson VE4002S1T2B3 DeltaV S-Series 8-Channel Analog Input Module
Emerson VE4002S1T2B3 DeltaV S-Series 8-Channel Analog Input Module
Emerson VE4002S1T2B3 DeltaV S-Series 8-Channel Analog Input Module
/ 3

Emerson VE4002S1T2B3 DeltaV S-Series 8-Channel Analog Input Module

  • Manufacturer: GE Fanuc

  • Part Number: VE4002S1T2B3

  • Condition:New with Original Package

  • Product Type: Analog Input Modules

  • Country of Origin: USA

  • Payment:T/T, Western Union

  • Shipping port: Xiamen

  • Warranty: 12 months

Emerson VE4002S1T2B3 DeltaV Analog Input Module

Configured for 4-20 mA field signal acquisition in DeltaV S-series architectures, the Emerson VE4002S1T2B3 (VE4002S1T2B3 Analog Input Module) provides direct physical/electrical execution. The module digitizes analog current loops via 16-bit analog-to-digital converters, transmitting process variables directly to the central system controller across the local bus interface.

Hardware Specifications

Parameter Specification
Model VE4002S1T2B3
Brand Emerson
Origin USA
Weight 0.5 kg
Dimensions 51 x 102 x 102 mm
Operating Temp -40 to +70 deg C
Power Consumption LocalBus: 12 VDC at 150 mA
Signal Range 4-20 mA current input
Resolution 16-bit analog-to-digital conversion
Number of Channels 8 galvanically isolated channels
HART Support Pass-through, point-to-point protocol
Bussed Field Power Rating 12 VDC at 300 mA
Field Circuit Rating 24 VDC at 32 mA
Storage Temperature -40 to +85 deg C
Relative Humidity 5% to 95% non-condensing
Environmental Ratings Airborne Contaminants ISA-S71.04 Class G3, IP20
Mechanical Resistance Shock: 10 g half-sine wave for 11 ms; Vibration: 1 mm peak-to-peak (2-13.2 Hz), 0.7 g (13.2-150 Hz)
Hazardous Location Ratings CE, UL, ATEX, IECEx (Zone 2 / Class I Div 2)

4-20 mA HART Loop Protocol and Channel Isolation

The VE4002S1T2B3 integrates dedicated channel-to-channel galvanic isolation across all 8 input paths, preventing ground loop currents and suppressing common-mode voltage spikes in distributed field wiring. The internal signal processing hardware supports the 4-20 mA HART loop protocol via point-to-point pass-through communication, allowing higher-level asset management software to extract digital diagnostic and configuration parameters directly from smart field transmitters without interrupting primary analog control signals.

Frequently Asked Questions

Q: Does the VE4002S1T2B3 support multi-drop HART network topologies?

A: No. The onboard HART communication hardware operates strictly in point-to-point pass-through mode, dedicated to single-device channel loops.

Q: How does channel-to-channel isolation benefit the module in harsh electrical environments?

A: Galvanic isolation breaks ground loops between separate transmitter loops, preventing electrical noise on one channel from interfering with adjacent analog measurements.

Q: What environmental protection levels are implemented on the circuit assembly?

A: The module conforms to ISA-S71.04 Class G3 requirements for airborne contaminants and carries an IP20 mechanical ingress rating.

Field Installation Guidelines

Mount the VE4002S1T2B3 module directly onto the designated DeltaV S-series I/O terminal block carrier until the retention latch snaps firmly into position. Route all 4-20 mA field wiring through shielded twisted-pair cables, ensuring signal cables remain physically separated from high-voltage AC power lines to avoid inductive noise coupling. Terminate cable shields at the central cabinet ground bar using a single-point connection. For installations operating in Class I Div 2 or Zone 2 hazardous locations, verify that the external cabinet maintains an IP54 or equivalent enclosure rating prior to energizing the 24 VDC field circuit.