Emerson VE4003S2B3 KJ4001X1-CC1 DeltaV DCS Analog Output Card
Emerson VE4003S2B3 KJ4001X1-CC1 DeltaV DCS Analog Output Card
Emerson VE4003S2B3 KJ4001X1-CC1 DeltaV DCS Analog Output Card
/ 3

Emerson VE4003S2B3 KJ4001X1-CC1 DeltaV DCS Analog Output Card

  • Manufacturer: GE Fanuc

  • Part Number: VE4003S2B3 KJ4001X1-CC1

  • Condition:New with Original Package

  • Product Type: Analog Output Modules

  • Country of Origin: USA

  • Payment:T/T, Western Union

  • Shipping port: Xiamen

  • Warranty: 12 months

Emerson VE4003S2B3 DeltaV Analog Output Card

The Emerson VE4003S2B3, also cataloged as the VE4003S2B3 KJ4001X1-CC1 Analog Output Card, operates as a dedicated hardware component for 4-20 mA analog signal execution within Emerson DeltaV DCS platforms.

Hardware Specifications

Parameter Specification
Model VE4003S2B3 KJ4001X1-CC1
Brand Emerson
Origin USA
Weight 0.20 kg
Dimensions 107 x 41 x 105 mm
Operating Temp -40 to +70 deg C
Power Consumption 24 VDC nominal
Output Channels 8 isolated output channels
Output Signal 4-20 mA analog output
Resolution 12-bit or higher
Accuracy +/-0.1% of span
Humidity Range 5% to 95% non-condensing
Shock Rating 10 g half-sine wave for 11 ms
Protection Class IP20
Hazardous Approvals Zone 2, Class I Div. 2

4-20 mA HART Loop Protocol & Channel-to-Channel Isolation

The module generates eight isolated 4-20 mA analog output loops to drive final control elements such as control valves and actuators. Galvanic channel-to-channel isolation prevents field ground loops and electrical noise from interfering with backplane signal processing. Integrated digital-to-analog converters deliver accurate current loop regulation across operating temperature variations. Furthermore, the hardware maintains continuous loop diagnostics, enabling real-time detection of open-circuit conditions and field wiring degradation while supporting HART loop communication transparency across DeltaV DCS networks.

Frequently Asked Questions

Q: Does the module support online hot-swapping during active DCS operation?

A: Yes, operators can replace the module on an energized DeltaV I/O carrier without isolating system power or interrupting adjacent channel communications.

Q: How does channel-to-channel isolation protect control loop signal integrity?

A: Internal galvanic barriers isolate each output channel electrically, preventing field voltage spikes or wiring short circuits on one loop from damaging neighboring channels or backplane electronics.

Field Installation Guidelines

Mount the card vertically into the designated DeltaV carrier slot until the locking retention lever fully locks into position. Connect field output cables to the terminal block using twisted-shielded pairs, grounding individual drain wires at the main cabinet earth bar only. Verify that all conduit entries maintain a minimum of 5 full threads engagement to satisfy Class I Div. 2 hazardous area requirements. Keep low-voltage 4-20 mA output wiring isolated from high-voltage AC power lines to avoid induced noise coupling.