{"product_id":"epro-con041-pr6423-009-031-cn-pr6423-eddy-current-proximity-sensor","title":"EPRO CON041+PR6423\/009-031-CN PR6423 Eddy Current Proximity Sensor","description":"\u003ch2\u003eEPRO CON041+PR6423\/009-031-CN Eddy Current Sensor System\u003c\/h2\u003e\n\u003cp\u003eConfigured for non-contact shaft vibration and displacement measurement in machinery protection systems, the \u003cstrong\u003eEPRO CON041+PR6423\/009-031-CN\u003c\/strong\u003e (\u003cstrong\u003eCON041\u003c\/strong\u003e Eddy Current Sensor System) provides direct physical\/electrical execution. The hardware assembly pairs an 8 mm probe head with an integrated signal conditioner, processing electromagnetic impedance transitions into linearized analog signals. This system directly links mechanical shaft dynamics to supervising monitoring networks without physical contact.\u003c\/p\u003e\n\u003ch3\u003eHardware Specifications\u003c\/h3\u003e\n\u003cfigure class=\"table\"\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr\u003e\n\u003cth\u003e\u003cstrong\u003eParameter\u003c\/strong\u003e\u003c\/th\u003e\n\u003cth\u003e\u003cstrong\u003eSpecification\u003c\/strong\u003e\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003eModel\u003c\/td\u003e\n\u003ctd\u003eCON041+PR6423\/009-031-CN\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eBrand\u003c\/td\u003e\n\u003ctd\u003eEPRO (Emerson)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOrigin\u003c\/td\u003e\n\u003ctd\u003eUnited States\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eWeight\u003c\/td\u003e\n\u003ctd\u003e0.32 kg\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eDimensions\u003c\/td\u003e\n\u003ctd\u003e12.1 cm x 5.2 cm x 16.6 cm\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOperating Temp\u003c\/td\u003e\n\u003ctd\u003eProbe: -35 to +180 deg C; Converter: -35 to +85 deg C\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003ePower Consumption\u003c\/td\u003e\n\u003ctd\u003ePower supply: 24 VDC nominal\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eProbe Tip Diameter\u003c\/td\u003e\n\u003ctd\u003e8 mm\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eLinear Measurement Range\u003c\/td\u003e\n\u003ctd\u003e2 mm (80 mils)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eSensitivity\u003c\/td\u003e\n\u003ctd\u003e8 V\/mm (203.2 mV\/mil) +\/- 5%\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eFrequency Response\u003c\/td\u003e\n\u003ctd\u003eUp to 10 kHz\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOutput Signal\u003c\/td\u003e\n\u003ctd\u003e4-20 mA DC \/ +\/-10 V DC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eProtection Class\u003c\/td\u003e\n\u003ctd\u003eProbe: IP66; Converter: IP20\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003c\/figure\u003e\n\u003ch3\u003eEddy-Current Probe Scaling and Gap Voltage Validation\u003c\/h3\u003e\n\u003cp\u003eThe dual-component hardware loop uses precise eddy-current probe scaling to guarantee an Incremental Scale Factor (ISF) of 8 V\/mm across the physical 2 mm operating range. Technicians perform gap voltage validation during physical commissioning, adjusting the 8 mm probe body relative to the target until the baseline output voltage of the CON041 converter stabilizes at its designated negative voltage target. This accurate calibration sequence counteracts dynamic rotor dynamics during startup and load cycles, while the internal shielding configuration guarantees high cross-talk suppression between adjacent probe lines.\u003c\/p\u003e\n\u003ch3\u003eFrequently Asked Questions\u003c\/h3\u003e\n\u003cp\u003eQ: How does the CON041 converter handle cabling fault diagnostics?\u003c\/p\u003e\n\u003cp\u003eA: The converter continuously evaluates circuit impedance, driving the 4-20 mA current output below 3.6 mA to signal a broken sensor wire or short-circuit condition immediately to the master system.\u003c\/p\u003e\n\u003cp\u003eQ: Can the CON041 converter module be installed in the same high-temperature environment as the PR6423\/009-031-CN probe?\u003c\/p\u003e\n\u003cp\u003eA: No. The PR6423\/009-031-CN probe tip is rated for up to +180 deg C, whereas the CON041 converter housing contains active processing circuitry and must be installed in a cooler area with ambient temperatures between -35 and +85 deg C.\u003c\/p\u003e\n\u003cp\u003eQ: Is the system output compatible with simultaneous voltage and current logging?\u003c\/p\u003e\n\u003cp\u003eA: Yes, the CON041 features separate output terminals allowing both the 4-20 mA DC loop and the +\/-10 V DC signal to be wired in parallel to separate monitoring or PLC\/DCS input modules.\u003c\/p\u003e\n\u003ch3\u003eField Installation Guidelines\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003e\n\u003cstrong\u003eProbe Gap Adjustment:\u003c\/strong\u003e Slowly screw the PR6423\/009-031-CN probe into the threaded mount while monitoring the analog voltage output until the physical air gap matches the calibrated 0.5 mm baseline.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eCable Protection:\u003c\/strong\u003e Encase the PTFE coaxial probe cable within flexible conduit to shield the run from mechanical crushing and fluid contamination.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eGrounding Protocol:\u003c\/strong\u003e Maintain single-point grounding by connecting the extension cable shield strictly at the CON041 converter terminal block and keeping the probe housing isolated from the machine frame.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eAvoid High-Voltage Paths:\u003c\/strong\u003e Route the signal cables away from high-current AC motor leads or switching frequency drives to prevent electromagnetic noise from distorting the analog outputs.\u003c\/li\u003e\n\u003c\/ul\u003e","brand":"Emerson","offers":[{"title":"Default Title","offer_id":44364425363555,"sku":"CON041+PR6423\/009-031-CN","price":0.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0583\/5246\/8067\/files\/11._80fdac40-6526-4d66-95dc-e74de924e528.jpg?v=1784105503","url":"https:\/\/www.autocontrolglobal.com\/products\/epro-con041-pr6423-009-031-cn-pr6423-eddy-current-proximity-sensor","provider":"AutoControl Global","version":"1.0","type":"link"}