Honeywell CC-TCNT01 Experion PKS Series C Thermocouple Input Module

The Honeywell CC-TCNT01, also cataloged as the CC-TCNT01 (Part Number 51308307-175) Thermocouple Analog Input Module, operates as a dedicated hardware component for 16-channel millivolt signal conversion and temperature loop execution within Honeywell Experion PKS Series C systems.

Hardware Specifications

Parameter Specification
Model CC-TCNT01 / 51308301-175 / 51308307-175
Brand Honeywell
Origin USA
Weight 0.18 kg
Dimensions 120 mm x 145 mm x 52 mm
Operating Temp -20 to 70 deg C
Power Consumption 24 VDC nominal supply (0.311 A current draw)
System Platform Honeywell Experion PKS Series C
Input Channels 16 isolated thermocouple channels
Supported Thermocouples Types J, K, T, E, R, S, B, N
Conversion Resolution 16-bit A/D conversion
Measurement Accuracy plus/minus 0.1% of full scale
Circuit Protection G3 conformal-coated printed wiring assembly
Mounting Type Series C I/O rack / IOTA carrier

4-20 mA HART Loop Protocol & Cold Junction Compensation

Engineers integrate the input module into distributed control networks requiring precise millivolt-to-digital signal processing across severe thermal environments. Integrated automatic Cold Junction Compensation (CJC) located directly at the terminal connection point compensates for ambient temperature shifts inside the panel enclosure. Channel-to-channel galvanic isolation blocks high-voltage ground loops and suppresses electromagnetic noise in furnace and turbine processing loops. Internal diagnostic routines continuously evaluate sensor circuit impedance to flag open-circuit burnout states without tripping adjacent control channels.

Frequently Asked Questions

Q: Does the CC-TCNT01 handle raw millivolt signal inputs directly?

A: Yes, in addition to standard IEC thermocouple curves, the analog front-end processes low-level millivolt signals directly from field transmitters.

Q: How does the G3 conformal coating protect the assembly in industrial environments?

A: The G3-rated coating seals the printed wiring assembly against airborne corrosive agents such as hydrogen sulfide and chlorine gas under high ambient humidity conditions.

Q: Can the module detect a broken sensor wire on a connected thermocouple loop?

A: Yes, onboard diagnostics automatically execute open-circuit burnout detection to trigger pre-configured safety states and diagnostic alerts within the Experion software platform.

Field Installation Guidelines

Mount the module on the designated Series C carrier rack or IOTA frame inside a grounded control cabinet. Maintain a minimum vertical spacing of 50 mm above and below the module to promote free convection airflow up to the 70 deg C thermal threshold. Connect thermocouple Extension wires to the IOTA screw terminals, observing strict polarity for the specific thermocouple alloy type. Terminate all cable shields to a dedicated earth ground rail at the enclosure base to prevent common-mode voltage buildup.