Foxboro AD201MZ I/A Series Analog I/O Module
Foxboro AD201MZ I/A Series Analog I/O Module
Foxboro AD201MZ I/A Series Analog I/O Module
/ 3

Foxboro AD201MZ I/A Series Analog I/O Module

  • Manufacturer: Foxboro

  • Part Number: AD201MZ

  • Condition:New with Original Package

  • Product Type: Analog I/O Modules

  • Country of Origin: USA

  • Payment:T/T, Western Union

  • Shipping port: Xiamen

  • Warranty: 12 months

Foxboro AD201MZ I/A Series Analog I/O Module

Configured for high-density analog signal processing in Foxboro I/A Series DCS networks, the Foxboro AD201MZ (AD201MZ Analog I/O Module) provides direct physical/electrical execution.

Hardware Specifications

Parameter Specification
Model AD201MZ
Brand Foxboro
Origin USA
Weight 0.29 kg
Dimensions Standard Foxboro I/A Series Form Factor
Operating Temp 0 to +60 deg C
Power Consumption Max 8.5 W
Channel Count 32 channels (analog input/output)
Supported Signal Types Voltage, current, RTDs, thermocouples
Conversion Resolution 16 bits
Measurement Accuracy +/-0.1% of full scale
Channel Scan Rate Up to 250 ms per channel
Channel Isolation 2 kV AC input/output isolation
Supply Input 24 VDC (supports redundant supply)
Onboard Diagnostics Integrated continuous hardware status checking

Cold Junction Compensation and 4-20 mA HART Loop Protocol

The Foxboro AD201MZ conditions analog voltage, current, RTD, and thermocouple signals across 32 individual channels, integrating cold junction compensation (CJC) algorithms to ensure precision temperature linearization. 2 kV galvanically isolated channels decouple field loop circuits from backplane logic power, maintaining 4-20 mA HART loop protocol signal integrity across high-density field wiring networks. The onboard 16-bit analog-to-digital converters execute continuous signal processing and self-diagnostics, driving stable process data updates to the supervisory host without introducing ground loop potential errors.

Frequently Asked Questions

Q: How does the AD201MZ handle cold junction compensation for thermocouple input channels?

A: Internal temperature sensors located on the field terminal assembly measure reference junction ambient values, allowing onboard algorithms to execute cold junction compensation adjustments before transmitting linearized 16-bit data to the processor.

Q: What power redundancy provisions exist for the AD201MZ module?

A: The module accepts dual 24 VDC supply lines through internal diode-ORing circuitry, maintaining continuous logic and field channel operation if one primary supply bus drops out.

Q: Is hot-swapping permitted during system operation?

A: Yes. The baseplate connector interface allows insertion and extraction of the AD201MZ module while backplane power remains energized, provided proper field terminal disconnection procedures are executed.

Field Installation Guidelines

  • Power Feeder De-energization: Verify 24 VDC bus lines are isolated before attaching or wiring field terminal blocks to prevent transient arcing.
  • Module Baseplate Insertion: Align the module card guides with the designated slot in the Foxboro I/A Series baseplate and seat the connector firmly until top and bottom mechanical latches engage completely.
  • Shield Wiring Terminal Grounding: Connect all individual thermocouple and 4-20 mA cable shield drain wires directly to dedicated terminal block shield lugs, tying them back to the central cabinet earth ground bar.
  • Thermocouple Cable Routing: Run thermocouple extension wires in isolated instrument wire trays, away from AC motor power cables or high-voltage lines, to eliminate inductive noise coupling.
  • Convection Thermal Venting: Maintain a minimum of 100 mm unobstructed clearance above and below the baseplate rack to allow natural thermal convection across internal heat-dissipating components.
You may also like