FS-TRO-1024 | Honeywell FSC Relay Output Assembly
FS-TRO-1024 | Honeywell FSC Relay Output Assembly
FS-TRO-1024 | Honeywell FSC Relay Output Assembly
/ 3

FS-TRO-1024 | Honeywell FSC Relay Output Assembly

  • Manufacturer: Honeywell

  • Part Number: FS-TRO-1024

  • Condition:New with Original Package

  • Product Type: Digital Output Field Termination Assemblies

  • Country of Origin: USA

  • Payment:T/T, Western Union

  • Shipping port: Xiamen

  • Warranty: 12 months

Honeywell FS-TRO-1024 Digital Output Relay Contact Field Termination Assembly

The Honeywell FS-TRO-1024, also cataloged as the FS-TRO-1024 Digital Output Relay Contact Field Termination Assembly, operates as a dedicated hardware component for relay-based signal switching within Honeywell FSC safety system networks. Configured for high-integrity load control in industrial control environments, this assembly routes controller output commands directly to external field actuators, solenoids, and alarm annunciators. The unit interfaces directly with redundant digital output modules via dedicated system interconnection cables, translating internal logic commands into physical relay contact states. Universal snap-in DIN rail mounting geometry allows efficient placement inside control cabinets. Standard screw terminal blocks facilitate robust field cable termination and loop distribution across process automation facilities.

Hardware Specifications

Parameter Specification
Model FS-TRO-1024
Brand Honeywell
Origin USA
Weight 0.3 kg
Dimensions 60 x 70 x 54 mm
Operating Temp -20 to 60 deg C
Power Consumption 5 VDC, 25 mA (WDG input current: 4 mA)
Channel Count 10 relay output channels
Output Specification Relay contact
Maximum Voltage 30 VAC / 36 VDC (IEC 61010-1)
Maximum Current 2 A
Maximum Load Capacitance 100 nF
Space Requirements 4 TE, 3 HE (4 HP, 3U)
Compatible Module Honeywell 10208/2/1 digital output module
Interconnection Cable SIC-C-12
Termination Type Screw terminals (up to 2.5 mm2 / AWG 14)
Mounting Type DIN rail (TS32 / TS35 x 7.5 mm)

Functional Safety & Relay Switching Integrity

Safety-instrumented systems (SIS) require robust isolation between low-voltage controller logic and higher-energy field loads. The FS-TRO-1024 provides 10 independent relay output channels designed to support high-reliability interlocking architectures. Each channel manages inductive and resistive loads up to 2 A, maintaining strict electrical isolation across channel boundaries to prevent cross-talk and transient feedback into the central processor backplane. The assembly incorporates fixed contact configurations compatible with redundant output module pairs, ensuring deterministic state execution during safety shutdown sequences. If a downstream fault occurs, the electromechanical separation protects internal control hardware from overvoltage surges and ground potential shifts.

Frequently Asked Questions

Q: How does the module interface with redundant digital output cards?

A: The assembly connects directly to dual Honeywell 10208/2/1 digital output modules using the standardized SIC-C-12 system interconnection cable, maintaining redundant signal paths for high-availability safety applications.

Q: What are the maximum electrical ratings for the relay output contacts?

A: Each of the 10 relay channels supports a maximum switching voltage of 30 VAC / 36 VDC in compliance with IEC 61010-1 standards, with a maximum continuous current limit of 2 A and a load capacitance threshold of 100 nF.

Q: Can maintenance personnel replace individual relay elements on the termination board?

A: The field termination assembly functions as an integrated terminal unit; individual relays are not field-replaceable components. Replacement requires swapping the complete assembly unit following standard plant lockout/tagout safety protocols.

Field Installation Guidelines

Mount the assembly securely onto a standard TS32 or TS35 x 7.5 mm DIN rail using the integrated snap-in mechanism, ensuring a minimum rail allocation of 61 mm. Secure end stoppers on both sides of the baseplate to prevent lateral shifting under high-vibration industrial conditions.

Route external field wiring through dedicated wire ducts, maintaining physical segregation between power distribution lines and low-voltage control signals. Strip conductor insulation to exactly 7 mm, insert the wire ends into the screw terminal blocks, and tighten each screw to a torque rating of 0.5 Nm. Ensure that wire gauges do not exceed 2.5 mm2 (AWG 14).

Verify system grounding before attaching the SIC-C-12 interconnection cable from the Honeywell output module. Check that all field devices connected to the 10 relay channels operate within the specified 30 VAC / 36 VDC and 2 A limits prior to energizing the control system power supplies.