  • Manufacturer: GE Fanuc

  • Part Number: IC200MDL650L

  • Condition:New with Original Package

  • Product Type: Digital Input Modules

  • Country of Origin: USA

  • Payment:T/T, Western Union

  • Shipping port: Xiamen

  • Warranty: 12 months

GE Fanuc IC200MDL650L VersaMax Discrete Input Module

The GE Fanuc IC200MDL650L, also cataloged as the IC200MDL650 Discrete Input Module, operates as a dedicated hardware component for digital signal acquisition within VersaMax I/O systems.

Hardware Specifications

Parameter Specification
Model IC200MDL650L (IC200MDL650)
Brand GE Fanuc
Origin USA
Weight 0.45 kg
Dimensions 110 x 66.8 x 50 mm
Operating Temp 0 to 60 deg C
Power Consumption 5 VDC at 50 mA max backplane current
Input Channels 32 points (4 groups of 8)
Input Signal Nominal 24 VDC positive logic
Input Voltage Range 0 to 30 VDC
On-State Voltage 15 to 30 VDC
Off-State Voltage 0 to 5 VDC
On-State Current 2.0 to 5.5 mA
Off-State Current 0.0 to 0.5 mA
Input Impedance 10 kOhm max
Response Time 0.5 ms default (configurable 0 ms, 1 ms, 7 ms filter)
Isolation 250 VAC continuous, 1500 VAC for 1 min (inputs to backplane)
Status Indicators 32 green point LEDs, 1 green backplane power OK LED

Backplane Bus Communication Velocity & I/O Density Scaling

The module transfers 32 discrete input state signals to the central CPU through high-density backplane bus communication velocity channels. Integrated optical isolation shields internal logic circuits and system processing units from high-voltage field spikes up to 1500 VAC. Dedicated hardware registers map input states directly into system memory each scan cycle without incurring field-side polling delay. Furthermore, individual channel response filters attenuate contact bounce and high-frequency line noise, ensuring deterministic signal updating across expandable I/O density carrier tracks.

Frequently Asked Questions

Q: Does replacing an IC200MDL650L module require resetting system power to the VersaMax carrier backplane?

A: No, field installation procedure permits hot-insertion and hot-removal of the module on active VersaMax I/O carriers while maintaining logic backplane continuity.

Q: How does input response filtering function across individual channel groups?

A: Software configuration updates filter constant registers to selectable 0 ms, 1 ms, or 7 ms intervals, suppressing noise artifacts before signal states commit to the backplane memory matrix.

Q: Can channels on the IC200MDL650L be wired for negative logic sensor configurations?

A: Standard IC200MDL650 hardware targets positive logic, while full native negative logic sourcing configurations require hardware revision IC200MDL650C or higher.

Field Installation Guidelines

Mount the IC200MDL650L module directly onto its assigned VersaMax I/O carrier interface rail until mechanical latches engage fully. Route field input conductors to individual terminal block pins, ensuring each group of 8 input channels connects through its designated common return rail. Maintain direct single-point grounding from the carrier backplane terminal bar to the enclosure earth ground bus using 14 AWG copper wire. Separate signal conductors from high-voltage power lines inside panel trunking by at least 100 mm to suppress electro-magnetic interference.